| Plan Review Notes For Permit 15030841 |
| Permit Number |
15030841 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-05-19 13:09:42 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY PLUMBING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE CLOTHES WASHER STANDPIPE AND DRAINAGE PIPE IS | | | REQUIRED TO BE A MINIMUM OF 2 INCHES. FBC-R P3201.7 | | | | | | 2) THE CLOTHES WASHER AND LAVATORY ARE REQUIRED TO BE | | | VENTED. FBC-R P3201.5 (3) | | | | | | 3) THE VENT FOR THE WATER CLOSET IS REQUIRED TO BE 2" | | | WHICH IS 1/2 THE SIZE OF THE 4" BRANCH DRAIN PIPE. | | | FBC-R P3113.1 | | | |
|