| Plan Review Notes For Permit 15030841 |
| Permit Number |
15030841 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-05-19 14:42:26 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS APPEAR TO SHOW THE ELECTRICAL PANEL | | | LOCATED IN THE WALL BEHIND THE CLOTHES DRYER, WHICH IS | | | NOT CODE COMPLIANT. NEC 110.26 SUFFICIENT ACCESS AND | | | WORKING SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT | | | ALL ELECTRICAL EQUIPMENT TO PERMIT READY AND SAFE | | | OPERATION AND MAINTENANCE OF SUCH EQUIPMENT. | | | | | | 2) SHOW COMPLIANCE WITH NEC 230.70 FOR SERVICE | | | DISCONNECTING MEANS. | | | | | | 3) THE ELECTRICAL RISER ON THE PLAN SHOWS A 200 AMP | | | DISCONNECT THAT DOES NOT MATCH THE SEVICE THAT IS SHOWN | | | ON THE EAST ELEVATION. FBC 107.2.1 | | | | | | 4) FBC- 107.3.5.3 - PROVIDE AN ELECTRIC SERVICE RISER | | | DIAGRAM WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING | | | DETAIL. | | | | | | 5) THE SMOKE ALARM OUTSIDE THE MASTER BEDROOM CAN NOT | | | BE LOCATED IN THE LAUNDRY ROOM/CLOSET. FBC-R314.3 | | | | | | |
|