Plan Review Notes
Plan Review Notes For Permit 15030841
Permit Number 15030841
Review Stop E
Sequence Number 2
Notes
Date Text
2015-05-19 14:42:26PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS APPEAR TO SHOW THE ELECTRICAL PANEL
 LOCATED IN THE WALL BEHIND THE CLOTHES DRYER, WHICH IS
 NOT CODE COMPLIANT. NEC 110.26 SUFFICIENT ACCESS AND
 WORKING SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT
 ALL ELECTRICAL EQUIPMENT TO PERMIT READY AND SAFE
 OPERATION AND MAINTENANCE OF SUCH EQUIPMENT.
  
 2) SHOW COMPLIANCE WITH NEC 230.70 FOR SERVICE
 DISCONNECTING MEANS.
  
 3) THE ELECTRICAL RISER ON THE PLAN SHOWS A 200 AMP
 DISCONNECT THAT DOES NOT MATCH THE SEVICE THAT IS SHOWN
 ON THE EAST ELEVATION. FBC 107.2.1
  
 4) FBC- 107.3.5.3 - PROVIDE AN ELECTRIC SERVICE RISER
 DIAGRAM WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING
 DETAIL.
  
 5) THE SMOKE ALARM OUTSIDE THE MASTER BEDROOM CAN NOT
 BE LOCATED IN THE LAUNDRY ROOM/CLOSET. FBC-R314.3
  
  