| Date |
Text |
| 2016-01-25 16:55:53 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. THE SQUARE FOOT AREA ON THE PLANS STAMPED BY PALM |
| | BEACH COUNTY HAS CHANGED. PLEASE HAVE THE PLANS |
| | STAMPED, AND PROVIDE (NEW) RECEIPT SHOWING THAT FEES |
| | WERE PAID, IF APPLICABLE. |
| | |
| | 2. PLAN SPECIFIES BOTH CONCRETE ROOF TILE (OFFICE AREA) |
| | AND A HOT MOP SYSTEM OVER THE FLAT ROOF. PRODUCT |
| | APPROVALS WERE NOT SUBMITTED FOR EITHER OF THOSE |
| | PRODUCTS. SEALOFLEX PRODUCT APPROVAL WAS SUBMITTED, |
| | CLARIFY LOCATION OF INSTALLATION, FBC 107. THIS MAY BE |
| | DONE VIA LETTER OR BY REVISING THE PLAN. |
| | |
| | THE ROOF PRODUCT APPROVALS CAN BE A PROVISO ITEM |
| | (PROVIDE WITH ROOF PERMIT APPLICATION, PRIOR TO |
| | INSTALLATION). WILL THE EXISTING ROOF HAVE THE |
| | SEALOFLEX SYSTEM INSTALLED? A MOISTURE SURVEY IS |
| | REQUIRED FOR A ROOF RECOVERY (INCLUDING COATINGS); THIS |
| | CAN ALSO BE A PROVISO ITEM. |
| | |
| | 3. REGARDING DOOR #1, THE MAIN ENTRY DOOR, THIS IS A |
| | PART OF AN ACCESSIBLE ROUTE, FBC 2010 ACCESSIBILITY |
| | 404.2.5, PROVIDE INFORMATION WHICH DEMONSTRATES |
| | COMPLIANCE WITH THE THRESHOLD HEIGHT (1/2" MAX) |
| | LIMITATION (PGT "FD-750 OUTSWING ALUMINUM FRENCH DOOR" |
| | NOA 14-1117.05. |
| | |
| | 4. THE FLORIDA STATE PRODUCT APPROVAL APROVIDED IS FOR |
| | 2014 CODE; GOVERNING CODE FOR THIS PROJECT IS FBC 2010. |
| | EITHER PROVIDE A PRODUCT APPROVAL FOR FBC 2010 OR |
| | REQUEST ALTERNATIVE MATERIALS AND METHODS FOR |
| | CONSIDERATION (FBC 104.11). |
| | |
| | |