| 2015-12-02 13:11:46 | 1ST REVIEW 2010 MECHANICAL |
| | PERMIT #15030795 |
| | 12/2/15 |
| | |
| | 1 ) COMMENT #2 FROM THE 1ST REVIEW WILL STAND BASED ON |
| | THE REVISED DRAWING INDICATING THE ADDITION OF AN |
| | ENCLOSED PARKING GARAGE ATTACHED TO THE CARPENTRY |
| | BUILDING. PLEASE REFER TO SECTION 406.3, 406.3.3.1, AND |
| | 406.4.2 FBC-10 BUILDING. SECTION 406.3.3.1: "FOR |
| | NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF THE |
| | STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS ON |
| | TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN |
| | EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20 |
| | PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER. |
| | THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE |
| | PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40 |
| | PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS |
| | SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY |
| | DISTRIBUTED OPENINGS." PER THE CODE SECTIONS LISTED |
| | ABOVE, THE BUILDING IS DEFINED AS AN "ENCLOSED GARAGE". |
| | I HAVE REPRINTED COMMENT #2 FROM THE 1ST REVIEW BELOW. |
| | 2) IN REFERENCE TO NEW PARKING GARAGES PLEASE REVIEW |
| | SECTION 404.1 FBC-10 MECHANICAL, AND PROVIDE CONTINUOUS |
| | MECHANICAL VENTILATION OR A VENTILATION SYSTEM DESIGNED |
| | TO OPERATE AUTOMATICALLY UPON DETECTION OF A |
| | CONCENTRATION OF CARBON MONOXIDE OF 25 PARTS PER |
| | MILLION (25 PPM) BY APPROVED AUTOMATIC DETECTION |
| | DEVICES (CO DETECTORS). PLEASE NOTE THAT AUTO OPERATION |
| | OF THE SYSTEM SHALL NOT REDUCE THE VENTILATION AIRFLOW |
| | RATE BELOW 0.05 CFM PER SQ. FT. OF THE FLOOR AREA AND |
| | THE SYSTEM SHALL BE CAPABLE OF PRODUCING A VENTILATION |
| | AIRFLOW OF 0.75 CFM PER SQ. FT. OF FLOOR AREA. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |