| 2016-01-29 10:17:42 | ISSUED WITH ELECTRICAL PROVISO: | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | | MEANS. NEC 110.16, 110.22 | | | PROVIDE HIGH LEG IDENTIFICATION AT THE ELECTRICAL | | | SERVICE AND PANEL BOARDS. NEC 408.3, 110.15, 230.56 | | | SERVICE NEUTRAL REQUIRED FOR 3 PHASE SERVICE. NEC | | | 250.24(C) | | | PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES | | | IN GARAGE. NEC 210.8 | | | PROVIDE A INTERSYSTEM BONDING BAR AT THE ELECTRICAL | | | SERVICE. NEC 250 .94 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | |
|