| 2015-12-16 15:06:55 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15030795 |
| | ADD: 5390 GEORGIA AVE. |
| | CONT: TIM GIVENS BUILDING |
| | TEL: (561)533-5825 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: WED. DEC. 16I/2015 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED. |
| | |
| | 4A)(1) SEMI- COMPLIED. THE PLANS DO NOT PROVIDE |
| | OCCUPANCY SEPARATION WALLS. PLEASE IDENTIFY THE |
| | OCCUPANCY SEPARATION WALLS BETWEEN THE F1 & S1 |
| | OCCUPANCIES AND HOUR RATING OF WALL AND OPENING |
| | PROTECTIVE. |
| | 2010 FBC-B TABLE 508.4 |
| | 2010 FBC-B TABLE 715.4. |
| | |
| | 4A)(2) COMPLIED. 1 ? HR. OPENING PROTECTION. DOOR # 4 |
| | IS SHOWN TO BE IN A 2 HOUR FIRE RATED WALL, THE DOOR |
| | SCHEDULE INDICATES THIS DOOR IS TO HAVE GLAZING IN THE |
| | DOOR, PLEASE PROVIDE THE AMOUNT OF SQ. INCHES IN THIS |
| | DOOR. 2010 FBC-B TABLE 715.5.4. |
| | |
| | 4B)NEW ISSUE: THE CARPENTRY WORK SHOP (F1 OCCUPANCY) |
| | AND S1 THE WOOD STORAGE DID NOT REQUIRE A FIRE BARRIER |
| | ( TABLE 508.4). THE NEW SET OF PLANS NOW SHOWS A CAR |
| | PARKED WITHIN THE SPACE PREVIOUSLY SHOWN AS A F1/ S1 |
| | OCCUPANCY. CAR STORAGE IN A RESIDENCE IS A U OCCUPANCY |
| | BUT IN A COMMERCIAL APPLICATION SECTION 2010 FBC-B |
| | 311.3 PUTS OPEN AND ENCLOSED GARAGES AS A S-2 LOW |
| | HAZARD. TABLE 508.4 WILL REQUIRE A 2 HR. WALL BETWEEN |
| | THE S2 ENCLOSED GARAGE AND THE F1 & S1 OCCUPANCIES. |
| | |
| | 4C) 2010 FBC-B 406.4.2 VENTILATION. A MECHANICAL |
| | VENTILATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH |
| | THE FLORIDA BUILDING CODE, MECHANICAL. |
| | |
| | 5-11) COMPLIED. |
| | |
| | 12) COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 13) NOTICE ONLY! THIS PROJECT HAS REQUESTED PRIVATE |
| | PROVIDER TEW & TAYLOR FOR ONSITE INSPECTIONS. FORMS |
| | HAVE BEEN SUBMITTED AND FILED OUT. |
| | |
| | 13A)NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM |
| | BEACHES AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS. |
| | |
| | 14) COMPLIED. IMPACT FEES PAID TO PALM BEACH COUNTY. |
| | JAMES A. WITMER CBO |