| 2015-09-04 12:54:01 | 2ND REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15030795 |
| | 9/4/15 |
| | |
| | 1) THE NEW ADDITION IS IDENTIFIED AS A NEW CARPENTRY |
| | STUDIO ON SHEET A-001, AND AS A NEW GARAGE ON ALL OTHER |
| | PLAN SHEETS. PLEASE MAKE ALL THESE PLANS MATCH ONE WAY |
| | OR THE OTHER. IF CONSTRUCTING A CARPENTRY STUDIO PLEASE |
| | PROVIDE AN EQUIPMENT FLOOR PLAN LAYOUT, EQUIPMENT |
| | SCHEDULE, AND A DUST COLLECTION SYSTEM IN COMPLIANCE |
| | WITH SECTION 511 FBC-10 MECHANICAL. |
| | 2) IN REFERENCE TO NEW PARKING GARAGES PLEASE REVIEW |
| | SECTION 404.1 FBC-10 MECHANICAL, AND PROVIDE CONTINUOUS |
| | MECHANICAL VENTILATION OR A VENTILATION SYSTEM DESIGNED |
| | TO OPERATE AUTOMATICALLY UPON DETECTION OF A |
| | CONCENTRATION OF CARBON MONOXIDE OF 25 PARTS PER |
| | MILLION (25 PPM) BY APPROVED AUTOMATIC DETECTION |
| | DEVICES (CO DETECTORS). PLEASE NOTE THAT AUTO OPERATION |
| | OF THE SYSTEM SHALL NOT REDUCE THE VENTILATION AIRFLOW |
| | RATE BELOW 0.05 CFM PER SQ. FT. OF THE FLOOR AREA AND |
| | THE SYSTEM SHALL BE CAPABLE OF PRODUCING A VENTILATION |
| | AIRFLOW OF 0.75 CFM PER SQ. FT. OF FLOOR AREA. |
| | 3) THE AIR HANDLER CLOSET SHALL HAVE A LOUVERED METAL |
| | DOOR FOR RETURN AIR- SECTION 603.1 FBC-10 MECHANICAL. |
| | THE ARCHITECTURAL PLANS INDICATE A SOLID WOOD PANELED |
| | DOOR. |
| | 4) A MIAMI DADE NOA (#14-0731.03) FOR AN ROOF TOP OR |
| | SIDEWALL EXHAUST FAN HAS BEEN SUBMITTED. THIS DOES NOT |
| | APPEAR TO BE THE EF-1 IN THE TOILET ROOM. PLEASE |
| | CLARIFY WHERE THE FAN IS TO BE LOCATED- IT IS NOT SHOWN |
| | ON THE PLAN |
| | |