Plan Review Notes
Plan Review Notes For Permit 15030793
Permit Number 15030793
Review Stop M
Sequence Number 2
Notes
Date Text
2015-06-12 10:45:302ND REVIEW: FBC 2010 MECHANICAL
  
 1) SHEET M-1: PROVIDE A DETAIL TO CLARIFY HOW THE 18
 X12 DUCT IS RUNNING FROM THE AHU DOWN TO THE FIRST
 FLOOR.
 2) M-1: SHOW THE DUCT RUN AND DUCT SIZE FROM THE MAIN
 DUCT TO THE BATHROOM ON THE SECOND FLOOR, AND INDICATE
 CFM SUPPLY AIR AT THE DIFFUSER.
 3) THE ENERGY CALCULATION FORM 405-10 MUST BE SIGNED
 AND DATED BY THE PREPARER AND BY THE OWNER.
 4) M-1: THE SEER OF THE PROPOSED UNIT IS NOT INDICATED
 IN THE AC SCHEDULE- IT IS LISTED AS 16 SEER IN THE
 ENERGY CALCS.
  