2015-05-26 11:05:1315030793
 231 ARGYLE ROAD
 RESIDENTIAL REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 IF THE BUILDING HAS GAS APPLIANCES, AN ATTACHED GARAGE
 OR A FIREPLACE, A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010
 FBC R314, 315
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH
 CIRCUITS SUPPLYING OUTLETS. NEC 210.12
 A GFCI PROTECTED RECEPTACLE IS REQUIRED AT THE FRONT
 ENTRANCE. NEC 210.8, 210.52(E) (1)
 INDICATE ON THE PLANS THE LOCATION OF ALL GFCI
 PROTECTED OUTLETS. NEC 210.8
 SHOW THE LOCATION OF THE ELECTRICAL SERVICE, PANELBOARD
 AND MAIN DISCONNECT ON THE BUILDING. VERIFY THE MAIN
 DISCONNECT IS LOCATED AT THE POINT OF SERVICE. VERIFY
 THE UNPROTECTED SERVICE CONDUCTORS ARE NOT LOCATED
 WITHIN THE BUILDING. NEC 230.70(A) (1)
 AN ELECTRICAL GROUNDING SYSTEM IS REQUIRED. NEC 250.24
 A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE
 GROUND. NEC 250.94
 PROVIDE A LOAD CALCULATION WHICH SUPPORTS THE SERVICE
 SIZE SELECTED. NEC 210.82
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  