| 2015-05-26 11:05:13 | 15030793 | | | 231 ARGYLE ROAD | | | RESIDENTIAL REMODEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | IF THE BUILDING HAS GAS APPLIANCES, AN ATTACHED GARAGE | | | OR A FIREPLACE, A CARBON MONOXIDE DETECTOR IS REQUIRED | | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010 | | | FBC R314, 315 | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH | | | CIRCUITS SUPPLYING OUTLETS. NEC 210.12 | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED AT THE FRONT | | | ENTRANCE. NEC 210.8, 210.52(E) (1) | | | INDICATE ON THE PLANS THE LOCATION OF ALL GFCI | | | PROTECTED OUTLETS. NEC 210.8 | | | SHOW THE LOCATION OF THE ELECTRICAL SERVICE, PANELBOARD | | | AND MAIN DISCONNECT ON THE BUILDING. VERIFY THE MAIN | | | DISCONNECT IS LOCATED AT THE POINT OF SERVICE. VERIFY | | | THE UNPROTECTED SERVICE CONDUCTORS ARE NOT LOCATED | | | WITHIN THE BUILDING. NEC 230.70(A) (1) | | | AN ELECTRICAL GROUNDING SYSTEM IS REQUIRED. NEC 250.24 | | | A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE | | | GROUND. NEC 250.94 | | | PROVIDE A LOAD CALCULATION WHICH SUPPORTS THE SERVICE | | | SIZE SELECTED. NEC 210.82 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | | | | |
|