2015-06-17 12:40:40RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1- SHEET S-1:
 A) ALL WALL SECTIONS AND DETAILS ARE MISSING THE
 STRUCTURAL CONNECTORS. SPECIFY ALL STRUCTURAL
 CONNECTIONS FOR ALL WOOD STUDS, WOOD COLUMNS, FLOOR
 JOISTS TO NEW STEEL BEAM, ETC. . SEC. R301.1 AND R601.2
 OF 2010 FBC-RESIDENTIAL.
  
 2- SECTION 5/S-1:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR THE TYPE OF
 STEEL BEAM. SQUARE BEAM? THICKNESS, ETC. SEC 107.2.1
 CITY AMENDMENTS.
  
 B) HOW MANY BOLTS ARE REQUIRED ON EACH STEEL ANGLE THAT
 IS SUPPORTING THE STEEL BEAM? SEC 107.2.1 CITY
 AMENDMENTS.
  
 C) STEEL ANGLE IS MISSING THE DIMENSION FOR ONE SIDE.
 SEC 107.2.1 CITY AMENDMENTS
  
 D) PROVIDE COMPLETE SPECIFICATIONS FOR THE TYPE OF
 FOUNDATION BEAM THAT WILL SUPPORT NEW STEEL BEAM. SEC
 107.2.1 CITY AMENDMENTS.
  
 3- SPECIFY TYPE AND SIZE OF EXISTING WINDOWS (SPECIALLY
 THE BEDROOM WINDOWS) AND TYPE AND SIZE OF PROPOSED
 WINDOWS TO VERIFY COMPLIANCE WITH SEC. 604 OF 2010
 FBC-EXISTING BUILDING.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOOR. PROVIDE 2 COPIES FLORIDA PRODUCT
 APPROVAL FL15255.5. ONLY ONE SUBMITTED. ALSO, IDENTIFY
 WHICH DOOR IS GOING TO BE INSTALLED TO VERIFY THE
 DESIGN PRESSURES CALCULATED BY THE DESIGNER OF RECORD.
  
 B) INSWING SIDE DOOR AS SHOWN ON PLANS BY THE KITCHEN
 AREA. NONE SUBMITTED AT THIS TIME.
  
 C) FRENCH DOOR. PROVIDE 2 COPIES. ONLY ONE WAS
 SUBMITTED.
  
 D) WINDOW MULLIONS. PROVIDE 2 COPIES. ONLY ONE
 SUBMITTED. AND, CLEARLY SPECIFY MULLION SIZE TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 E) SINGLE HUNG WINDOWS. PROVIDE 2 COPIES. ONLY ONE
 SUBMITTED.
  
 F) ALL STRUCTURAL CONNECTORS SPECIFIED ON WALL SECTIONS
 ON SHEET S-1. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 NUMBER AND PAGE SHOWING THE SPECIFIED CONNECTOR. OR
 LIST THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED BY THE NEW DESIGNER OF RECORD NOT FERNANDO
 GOMEZ-PINA, P.E.
  
 6- ENERGY CALCULATIONS SUBMITTED;
 A) NEED INFORMATION FROM PERSON COMPLETING THE FORM.
 SEC 405.4 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) NEED OWNER/AGENT SIGNATURE AND DATE AT BOTTOM OF
 FORM. SEC. 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) COMPLETE ALL THE INFORMATION ON TOP OF
 FORM,INCLUDING OWNER'S NAME AND BUILDER. SEC. 107.2.1
 CITY AMENDMENTS
  
 D) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION.
 SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 E) ITEM #8 IS INCORRECT. ACCORDING TO PLANS THERE IS
 NOT SLAB ON GRADE.
  
 F) ITEM # 9 IS INCORRECT. ACCORDING TO PLANS THERE ARE
 NOT CONCRETE BLOCK WALLS.
  
 G) ROOF MATERIAL SPECIFIED ON PAGE 2 OF 5 IS INCORRECT.
 THERE IS NOT BARREL TILE ON THIS HOUSE.
  
 H) DOOR TYPE ON PAGE 3 OF 5 IS INCORRECT. THERE ARE NOT
 WOOD DOORS. SEE PLANS AND PRODUCT APPROVALS SUBMITTED.
  
 NOTE: THIS IS A CONTRIBUTING HISTORIC HOUSE. ENERGY
 CALCULATIONS ARE NOT REQUIRED. BUT, IF THEY ARE
 SUBMITTED, THEY NEED TO BE CORRECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT