Plan Review Notes
Plan Review Notes For Permit 15030786
Permit Number 15030786
Review Stop P
Sequence Number 1
Notes
Date Text
2015-04-12 06:18:451) SUBMIT SANITARY / GREASE/ WATER RISER DIAGRAMS FOR
 ALL NEW WORK AND CHANGES TO THE EXISTING WATER AND
 SANITARY SYSTEM. SHOW ALL INDIRECT WASTES ON THE
 PLUMBING RISER , WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 2) SUBMIT A GAS RISER DIAGRAM FOR ALL NEW WORK OR
 CHANGES TO THE GAS SYSTEM. INDICATE PSI OF GAS, TYPE OF
 MATERIAL, TOATL DEVELOPED LENGTH TO MOST REMOTE OUTLET,
 ETC.WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 3) SUBMIT 2 COPIES OF MANUF. SPECIFICATIONS FOR ALL GAS
 EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND LABELED
 PER THE 2010 FUEL GAS CODE SEC. 301.3.
 4) SHT.1.1 (A) - THERE IS A LIST OF ALL THE KITCHEN
 EQUIPMENT IN A TABLE LABELED "ELECTRIC SCHEDULE."
 CLARIFY. IDENTIFY THE PIECES OF EQUIPMENT ON THIS
 SCHEDULE AS NEW OR EXISTING OR IDENTIFY THE EQUIPMENT
 AS SUCH ON THE FLOOR PLAN.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 5) SUBMIT 2 COPIES OF MANUF. SPECIFICATIONS FOR THE
 GREASE INTERCEPTOR UNIT. WPB AMEND.TO 2010 FBC SEC.
 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  