Plan Review Notes
Plan Review Notes For Permit 15030786
Permit Number 15030786
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-03-20 12:55:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PLAN INDICATES INCORRECT REFERENCES TO
 THE FLORIDA FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
  
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) THE SUBMITTED PLAN DOES NOT CONTAIN A LIFE SAFETY
 PLAN. PLEASE SUBMIT A LIFE SAFETY PLAN INCLUDING, FIRE
 WALLS, OCCUPANY LOADS FOR EACH SPACE, EGRESS PATHS,
 COMMON PATHS OF TRAVEL, EMERGENCY LIGHTS, FIRE
 EXTINGUSHER LOCATIONS, EXITS AND EXIT WIDTHS, LOCATIONS
 OF A PUBLIC WAY, ETC
  
 3) ADDITIONAL COMMENTS MAY BE GENERATED BASED ON
 SUBMITTAL OF THE ABOVE INFORMATION.
  