| Plan Review Notes For Permit 15030786 |
| Permit Number |
15030786 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-20 12:55:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SUBMITTED PLAN INDICATES INCORRECT REFERENCES TO | | | THE FLORIDA FIRE CODE. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | | | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 13, 2010 EDITION. | | | | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2010 EDITION. | | | | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2009 EDITION. | | | | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | | | 2) THE SUBMITTED PLAN DOES NOT CONTAIN A LIFE SAFETY | | | PLAN. PLEASE SUBMIT A LIFE SAFETY PLAN INCLUDING, FIRE | | | WALLS, OCCUPANY LOADS FOR EACH SPACE, EGRESS PATHS, | | | COMMON PATHS OF TRAVEL, EMERGENCY LIGHTS, FIRE | | | EXTINGUSHER LOCATIONS, EXITS AND EXIT WIDTHS, LOCATIONS | | | OF A PUBLIC WAY, ETC | | | | | | 3) ADDITIONAL COMMENTS MAY BE GENERATED BASED ON | | | SUBMITTAL OF THE ABOVE INFORMATION. | | | |
|