Plan Review Notes
Plan Review Notes For Permit 15030786
Permit Number 15030786
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-25 07:18:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030786
 ADD: 2808 N. AUSTRALIAN AVE.
 CONT: CLAY KOHLMEYER
 TEL: (561)694-1214
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: WED. MARCH 25/ 2015
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS DO NOT SHOW THE EXISTING
 CONDITIONS, AREA TO BE REMODELED, THE PLANS SUBMITTED
 SHEET 1.0A DOESN'T REFLECT WHAT HAS CHANGED ,JUST THAT
 IT IS NEW.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
  
 2) SHEET 1.0A. WITHIN THE FLOOR PLAN WHERE THE THROUGH
 THE WALL HOOD EXHAUST VENT IS LOCATED, IT APPEARS THERE
 WAS A RAMP ON THE EXTERIOR OF THE BUILDING, PLEASE
 PROVIDE WHAT THIS AERA IS AND WAS THERE A DOOR WAY
 THERE.107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET 1.0A DOES NOT SHOW HOW THE EXHAUST FAN IS
 GOING TO BE CUT THROUGH THE WALL AND THERE IS NO DETAIL
 OF HOW THE HOLE IS TO BE CREATED AND MAINTAINED WEATHER
 TIGHT. 2010 FBC-B 1403.2 WEATHER PROTECTION. EXTERIOR
 WALLS SHALL PROVIDE THE BUILDING WITH A
 WEATHER-RESISTANT EXTERIOR WALL ENVELOPE.
  
 4) THE PROPOSED WORK SHOWN ON SHEET 1.0A ALSO SHOWS A
 WALK IN COOLER ON THE INTERIOR OF THE BUILDING WITH
 WHAT APPEARS IS A ADDITION TO THE COOLER TO THE
 EXTERIOR OF THE BUILDING.
  
 4A) THE PLANS DO NOT INDICATE WHEN THE ADDITION OF THE
 EXTERIOR COOLER IS ADDED HOW THE PENETRATION OF THE
 WALL IS MADE, ASSUMED MATERIAL TO BE CBS CONSTRUCTION,
 EITHER COLUMNS WOULD BE CUT OR MASONRY CELLS WITH
 STEEL. THE SUPPORTING BEAM WAS NOT DESIGNED TO BE A
 CLEAR SPAN LOAD BEARING BEAM NOR DOES THE PLANS SHOW
 THE SUPPORTING COLUMNS. 2010 FBC-B 2107.1 GENERAL. THE
 DESIGN OF MASONRY STRUCTURES USING ALLOWABLE STRESS
 DESIGN SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTERS 1
 AND 2 OF TMS 402/ACI 530/ASCE 5 EXCEPT AS MODIFIED BY
 SECTION 2107.2.
  
 4B) SHEET 1.0A INDICATES THE NEW EXTERIOR COOLER WILL
 BE CONSTRUCTED, THERE IS NO INFORMATION, IF THE SLAB IS
 EXISTING, THICKNESS, NOR IS THERE INFORMATION AS TO THE
 WIND SPEED THE NEW EXTERIOR COOLER IS TO BE
 CONSTRUCTED.
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 4B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 4B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4B)(5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) SUBMIT PRODUCT APPROVALS: 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31) (G) EXTERIOR COOLER, FREEZERS &
 PRE-ENGINEERED A/C STANDS
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) THE PLANS DO NOT INDICATE IF THERE IS ANOTHER AREA
 THAT HAS BECOME THE DINING ROOM, PLEASE SUBMIT A LIFE
 SAFETY PLANS OF THE WHOLE BUILDING.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: LIFE SAFETY
 PLAN.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  