| 2015-03-25 07:18:35 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15030786 |
| | ADD: 2808 N. AUSTRALIAN AVE. |
| | CONT: CLAY KOHLMEYER |
| | TEL: (561)694-1214 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | 1ST REVIEW |
| | DATE: WED. MARCH 25/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLANS DO NOT SHOW THE EXISTING |
| | CONDITIONS, AREA TO BE REMODELED, THE PLANS SUBMITTED |
| | SHEET 1.0A DOESN'T REFLECT WHAT HAS CHANGED ,JUST THAT |
| | IT IS NEW. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. |
| | |
| | 2) SHEET 1.0A. WITHIN THE FLOOR PLAN WHERE THE THROUGH |
| | THE WALL HOOD EXHAUST VENT IS LOCATED, IT APPEARS THERE |
| | WAS A RAMP ON THE EXTERIOR OF THE BUILDING, PLEASE |
| | PROVIDE WHAT THIS AERA IS AND WAS THERE A DOOR WAY |
| | THERE.107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) SHEET 1.0A DOES NOT SHOW HOW THE EXHAUST FAN IS |
| | GOING TO BE CUT THROUGH THE WALL AND THERE IS NO DETAIL |
| | OF HOW THE HOLE IS TO BE CREATED AND MAINTAINED WEATHER |
| | TIGHT. 2010 FBC-B 1403.2 WEATHER PROTECTION. EXTERIOR |
| | WALLS SHALL PROVIDE THE BUILDING WITH A |
| | WEATHER-RESISTANT EXTERIOR WALL ENVELOPE. |
| | |
| | 4) THE PROPOSED WORK SHOWN ON SHEET 1.0A ALSO SHOWS A |
| | WALK IN COOLER ON THE INTERIOR OF THE BUILDING WITH |
| | WHAT APPEARS IS A ADDITION TO THE COOLER TO THE |
| | EXTERIOR OF THE BUILDING. |
| | |
| | 4A) THE PLANS DO NOT INDICATE WHEN THE ADDITION OF THE |
| | EXTERIOR COOLER IS ADDED HOW THE PENETRATION OF THE |
| | WALL IS MADE, ASSUMED MATERIAL TO BE CBS CONSTRUCTION, |
| | EITHER COLUMNS WOULD BE CUT OR MASONRY CELLS WITH |
| | STEEL. THE SUPPORTING BEAM WAS NOT DESIGNED TO BE A |
| | CLEAR SPAN LOAD BEARING BEAM NOR DOES THE PLANS SHOW |
| | THE SUPPORTING COLUMNS. 2010 FBC-B 2107.1 GENERAL. THE |
| | DESIGN OF MASONRY STRUCTURES USING ALLOWABLE STRESS |
| | DESIGN SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTERS 1 |
| | AND 2 OF TMS 402/ACI 530/ASCE 5 EXCEPT AS MODIFIED BY |
| | SECTION 2107.2. |
| | |
| | 4B) SHEET 1.0A INDICATES THE NEW EXTERIOR COOLER WILL |
| | BE CONSTRUCTED, THERE IS NO INFORMATION, IF THE SLAB IS |
| | EXISTING, THICKNESS, NOR IS THERE INFORMATION AS TO THE |
| | WIND SPEED THE NEW EXTERIOR COOLER IS TO BE |
| | CONSTRUCTED. |
| | WIND DESIGN CRITERIA |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | |
| | 4B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 4B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE |
| | 7-10. |
| | |
| | 4B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 4B)(5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 5) SUBMIT PRODUCT APPROVALS: 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (31) (G) EXTERIOR COOLER, FREEZERS & |
| | PRE-ENGINEERED A/C STANDS |
| | |
| | 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) THE PLANS DO NOT INDICATE IF THERE IS ANOTHER AREA |
| | THAT HAS BECOME THE DINING ROOM, PLEASE SUBMIT A LIFE |
| | SAFETY PLANS OF THE WHOLE BUILDING. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE |
| | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE |
| | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: LIFE SAFETY |
| | PLAN. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |