| Plan Review Notes For Permit 15030744 |
| Permit Number |
15030744 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-06-12 14:15:36 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | 1) THERE ARE INCORRECT REFERENCES TO THE FIRE CODE; | | | HOWEVER, THEY DO NOT APPEAR TO NEGATIVELY AFFECT THE | | | PROJECT. PLEASE ENSURE THAT THE PROJECT MEETS THE | | | APPROPRIATE REFERNECE AT THE TIME OF INSPECTION AND | | | CORRECT YOUR RECORDS FOR FUTURE SUBMITTALS. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 13, 2010 EDITION. | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2010 EDITION. | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2009 EDITION. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | | | | | | 2) THE DOOR TO THE BATHROOM SWINGS OUT INTO THE EXIT | | | CORRIDOR. THE DOOR CAN NOT SWING OUT TO MORE THAN HALF | | | OF THE REQUIRED EXIT WIDTH. THE SHALL BE SELF CLOSING | | | OR SWING IN TO THE BATHROOM. | | | |
|