| Date |
Text |
| 2015-05-14 14:44:08 | DISPOSITION AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN | | | REVIEW | | | APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010 | | | CHAPTER 1; NEC 2008 | | | REVIEW CYCLE: 2ND REVIEW, MIKE ALBARRAN | | | ACTION: FAILED, THIS ELECTRICAL REVIEW FAILED AS | | | OUTLINED BELOW: | | | 1. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN | | | OUTLET AT EVERY ENTRANCE. | | | 2. NEC 210.62 REQUIRES THAT THERE BE AN SHOW WINDOW | | | OUTLET FOR EVERY 12' OF SHOW WINDOW OR FRACTION | | | THEREOF. THIS OUTLET SHALL BE WITHIN 18" FROM THE TOP | | | OF THE WINDOW. | | | 3. AN EXIT LIGHT SHALL BE PLACED IN THE AREA OF COMMON | | | PATH OF EGRESS TRAVEL INDICATING EXIT TO EITHER | | | DIRECTION. | | | 4. COMPLIANCE W/FBC ENERGY CONSERVATION SECTION 505 | | | SHALL BE REQUIRED. | | | |
|