| Notes |
| Date |
Text |
| 2015-03-25 09:36:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PROVIDE A LIFE SAFTY PLAN SHOWING EXITS, EXIT LIGHTS, | | | EMERGENCY LIGHTS, EXIT DOOR HARDWARE, FIRE | | | EXTINGUISHERS, OCCUPANY LOADS, EGRESS PATHS, COMMON | | | PATHS OF TRAVEL, FIRE ALARM DEVICE LOCATIONS, ETC. | | | | | | PROVIDE EXISTING LIFE SAFETY SYSTEMS, I.E. FIRE ALARM & | | | FIRE SPRINKLER. IF LIFE SAFETY SYSTEMS EXIST, PROVIDE A | | | NOTE INDICATING: THE NATURE OF THE REMODEL REQUIRES AN | | | EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR | | | CODE COVERAGE AND COMPLIANCE. | | | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED. | | | |
|