| Plan Review Notes For Permit 15030727 |
| Permit Number |
15030727 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-21 11:52:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FBC 107, FBC 2010 RESIDENTIAL 301, FBC 2010 EXISTING | | | BUILDING 101.5: | | | | | | DESIGNER TO ELECT A METHOD OF COMPLIANCE | | | PROVIDE AN ARCHITECTURAL QUALITY STRUCTURAL DETAIL FOR | | | PROPOSED REPAIR | | | WIND DESIGN CRITERIA | | | | | | 2. IF PLANS ARE NOT PREPARED BY A DESIGN PROFESSIONAL, | | | PLANS TO INCLUDE PRINTED NAME AND SIGNATURE OF THE | | | INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN. | | | | | | IF PLANS ARE NOT PREPARED BY A DESIGN PROFESSIONAL, | | | CALCULATIONS MAY BE REQUIRED. | | | |
|