| 2015-04-08 09:57:30 | PROVIDE AN ELECTRICAL PERMIT APPLICATION ALONG WITH | | | ADDITIONAL ELECTRICAL PLANS TO INCLUDE THE FOLLOWING: | | | | | | 1) THE LOCATION OF THE ELECTRICAL PANEL THAT WILL | | | PROVIDE THE NEW CIRCUITRY REQUIRED FOR THE WATER HEATER | | | AND DISHWASHER. WPB AMENDMENTS TO THE FBC 107.3.2 | | | 2) THE PANEL SCHEDULE INDICATING THE EXISTING CIRCUITRY | | | AND THE NEW ADDITIONAL CIRCUITS REQUIRED FOR THE NEW | | | WATER HEATER AND DISHWASHER. NEC 408.4 | | | 3) A LOAD CALCULATION TO INDICATE THE ALLOWABLE | | | CAPACITY FOR THE ADDITIONAL LOAD PROPOSED. NEC 215.5 | | | 4) INDICATE THE USE OF AN DISCONNECTING MEANS FOR THE | | | WATER HEATER AS OPPOSED TO THE RECEPTACLE SHOWN | | | CURRENTLY. NEC 422.31 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|