| Plan Review Notes For Permit 15030671 |
| Permit Number |
15030671 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-28 11:10:56 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- RETURN AIR CAN NOT BE TAKEN FROM THE KITCHEN. SEC. | | | M1602.2 FBC-RESIDENTIAL. | | | | | | 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE A/C PLANS DESIGN. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|