Plan Review Notes
Plan Review Notes For Permit 15030671
Permit Number 15030671
Review Stop B
Sequence Number 1
Notes
Date Text
2015-04-24 18:17:43RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 4/28/15 DOUG HARVEY TALKED TO MIGUEL DE DIEGO
 (ARCHITECT). SECOND FLOOR STORAGE ADDITION WILL BE
 REVISED TO FUTURE MASTER BEDROOM.
 (COMMENTS BELOW ARE BASED ON THE CURRENT PLANS SHOWING
 "STORAGE").
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1006
 OF 2010 FBC-EXISTING BUILDING.
  
 3- PROVIDE COMPLETE WALL LEGEND. SPECIFY WHICH ARE
 EXISTING WALLS TO REMAIN, EXISTING WALLS TO BE REMOVED
 AND NEW WALLS. SPECIFY CONSTRUCTION OF NEW WALLS AND
 CLEARLY IDENTIFY ON PLANS ALL SCOPE OF WORK. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE STAIRS AND HANDRAILS SHOWING
 COMPLIANCE WITH SEC. R311.7 AND THE LIVE LOAD OF TABLE
 R301.5 OF 2010 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE FIREBLOCKING IN THE STAIRS AS
 REQUIRED BY SEC. R302.11 OF 2010 FBC-RESIDENTIAL.
  
 6- FLOOR PLANS SHOW BEDROOM #2 AND BEDROOM #3, WHERE IS
 BEDROOM #1?. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- CLARIFY IF WINDOW "A" ON BEDROOM #3 IS A REPLACEMENT
 OR NEW WINDOW. IF REPLACEMENT, THEN SPECIFY TYPE AND
 SIZE OF EXISTING WINDOW TO VERIFY COMPLIANCE WITH SEC.
 604 OF 2010 FBC-RESIDENTIAL. IF NEW, THEN THE WINDOW
 DOESN'T COMPLY WITH SEC. R310.1.1 OF
 2010-FBC-RESIDENTIAL. ACCORDING TO LAWSON INDUSTRIES
 SPECS 26 1/2" X 63" DOESN'T COMPLY WITH EGRESS SEC.
 R310.1.1.
 (NOTE: PLANS WILL BE REVISED. ADDITION WILL BE FOR
 FUTURE MASTER BEDROOM NOT STORAGE. VERIFY THAT WINDOWS
 WILL MEET THE EGRESS REQUIREMENTS WHEN REVISING PLANS).
  
 8- TYPICAL WALL SECTION ON SHEET 5/7:
 A) PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR ATTIC
 VENTILATION SHOWING COMPLIANCE WITH SEC. R806 OF 2010
 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLIANCE WITH THE FLAME SPREAD INDEX AND
 SMOKE DEVELOPED INDEX FOR EXPOSED INSULATION AS
 REQUIRED BY SEC. R302.10.1 OF 2010 FBC-RESIDENTIAL.
  
 C) PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 SECOND FLOOR CONSTRUCTION. SPECIFY FLOORING MATERIALS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 D) PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 FIREBLOCKING SHOWING COMPLIANCE WITH SEC. R302.11 OF
 2010 FBC-RESIDENTIAL.
  
 E) PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH SEC.
 R703.1.3 OF 2010 FBC-RESIDENTIAL.
  
 F) THE FIRST FLOOR OF THIS HOUSE IS WOOD FRAMING WALLS.
 CLARIFY HOW IS THE 1/2" WEDGE ANCHOR ATTACHED TO THE
 WOOD WALL AND EMBEDDED NOT LES THAN 7". SEC. 107.2.1
 CITY AMENDMENTS.
  
 G) CLARIFY IF THE PLYWOOD SHEATHING IS FOR THE WALL
 SHEATHING OR ROOF SHEATHING. SEC. R107.2.1 CITY
 AMENDMENTS. ROOF SHEATHING REQUIRES 8D RING SHANK
 NAILS. SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL AND THE
 MIN. DIMENSION FOR END AND CORNER ZONES IS 4'-0". SEE
 FOOTNOTE ON FIGURE R301.2(7) OF 2010 FBC-RESIDENTIAL.
  
 H) CLARIFY NOTE "SECURED TO CONC. FTG" THAT IS BELOW
 "R-19 INSULATION TYP". WHAT'S IS SECURED TO THE
 CONCRETE FOOTING?. IS THIS A TYPO?. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF THE "PREFAB DORMER"
 SHOWN ON NORTH ELEVATION TO SHOW COMPLIANCE WITH SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 10- DESIGN LOADS SHOWN ON SHEET 7/7 DON'T MATCH DESIGN
 LOADS SHOWN ON SHEET S-1. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 11- DESIGN CRITERIA ON SHEET S-1:
 A) ENGINEER TO CLARIFY WHY THE INTERNAL PRESSURE IS NOT
 APPLICABLE. SEC. 27.2.1 OF ASCE 7-10.
  
 B) ENGINEER TO SPECIFY THE LIVE AND DEAD LOADS FOR THE
 SECOND FLOOR STORAGE ROOM. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 C) ENGINEER TO SPECIFY THE WINDOWS DESIGN PRESSURES
 TRIBUTARY AREA OF AT LEAST 10 S.F. NOT 20 S.F. FOR
 EXAMPLE WINDOWS ON THE SECOND FLOOR ARE ON THE END ZONE
 AND THE SIZES OF WINDOWS ARE NOT 20 S.F. SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
  
 12- SHEET S-2:
 A) ENGINEER TO CLARIFY WHY THE SPACING OF THE 2X10
 FLOOR JOIST IS CLOSER ON THE UPPER LEFT HAND SIDE. IS
 THIS SPACE DESIGNED FOR AN SPECIAL STORAGE? SPECIFY
 SPACING. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 B) FLOOR FRAMING PLANS. CLEARLY IDENTIFY ALL NEW BEAMS
 ON BOTH FRAMING PLANS. AND SPECIFY ALL END CONNECTORS.
 SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 C) CLEARLY IDENTIFY ALL BEARING WALLS AND PROVIDE
 COMPLETE SPECIFICATIONS FOR THE BEARING WALLS. SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 D) PROVIDE COMPLETE ROOF FRAMING PLAN AND SPECIFY ALL
 CONNECTORS. NOTE: SIMPSON H10A CONNECTOR DOESN'T MEET
 THE DESIGN PRESSURES FOR THE TRUSS GIRDERS. SEE TRUSS
 PACKAGE. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 E) TRUSS PACKAGE SHOWS A ROOF FRAMING LAYOUT WITH A
 TRAY TOP AT 21'-0". CLARIFY WHY IS THIS TRAY REQUIRED
 FOR THE SECOND FLOOR STORAGE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 F) PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR ROOF
 SHEATHING. NOTE: NEED TO SPECIFY MIN. 8D RING SHANK
 NAILS. SEE SEC. R803.2.3.1 OE 2010 FBC-RESIDENTIAL.
  
 13- A) PROVIDE COMPLETE WALL SECTION SHOWING HOW ARE
 THE LOADS TRANSFERED FROM THE ROOF TO THE FOOTING.
 SPECIFY ALL CONNECTORS. SEC. R601.2 OF 2010
 FBC-RESIDENTIAL. NOTE: COORDINATE WITH TYPICAL WALL
 SECTION ON SHEET 5/7.
  
 B) KEY ON THE FRAMING PLANS WHERE ARE ALL THE DETAILS
 SHOWN ON S-3 TAKEN AT? SEC. 107.2.1 CITY AMENDMENTS.
  
 14- TRUSS PACKAGE:
 A) TRUSS PACKAGE DOESN'T COMPLY WITH SEC. 61G15-31.003
 F.A.C.. NEEDS THE INFORMATION OF THE PROFESSIONAL OF
 RECORD. NEEDS THE INFORMATION OF THE TRUSS DESIGN
 ENGINEER IN ALL SHEETS..
  
 B) TRUSS PACKAGE TO BE REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD. SEC. 61G15-30.005. F.A.C.
  
 NOTE: TRUSS PACKAGE NEED NOT BE RE-SUBMITTED AT THIS
 TIME. REVISED TRUSS PACKAGE MAY BE PRESENTED TO THE
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
  
 15- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL RELOCATED WINDOWS. THEY NEED TO COMPLY WITH THE
 DESIGN PRESSURES AND IMPACT PROTECTION REQUIREMENTS.
  
 B) HURRICANE IMPACT PROTECTION SYSTEM SUBMITTED.
 PROVIDE ONLY THE MIAMI-DADE NOA 12-1004.02 OR THE
 FLORIDA PRODUCT APPROVAL 15208-R0. THE DRAWINGS OF THE
 MIAMI-DADE NOA ARE TOO SMALL. PLEASE PRINT THEM IN
 LANDSCAPE FORM INSTEAD OF PORTRAIT SO THE DRAWINGS ARE
 LEGIBLE. OR PROVIDE THE COMPLETE LEGIBLE DRAWINGS FOR
 THE FLORIDA PRODUCT APPROVAL COVER PAGE SUBMITTED.
  
 C) WINDOW MULLIONS. AND CLEARLY IDENTIFY MULLION SIZE
 TO VERIFY DESIGN PRESSURES.
  
 D) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON TYPICAL
 WALL SECTION AND ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON ALL FRAMING PLANS AND DETAILS. PROVIDE
 ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE CONNECTOR OR LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 16- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 17- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF THE HURRICANE IMPACT PROTECTION SYSTEM
 SUBMITTED. SEE CITY SAMPLE OF INSTALLATION SCHEDULE OR
 PROVIDE COMPLETE INFORMATION ON A DIFFERENT FORMAT.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 18- SHOW LOCATION AND SIZE OF ATTIC ACCESS AT THE
 LIVING ROOM AREA. SEC. R807 OF 2010 FBC-RESIDENTIAL.
  
 19- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONALS FEES AS REQUIRED BY SEC. 109.33 CITY
 AMENDMENTS. REVISE VALUATION TO INCLUDE ALL SCOPE OF
 WORK SHOWN ON PLANS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE AND REPLACE ANY REVISED SHEET.
 PROVIDE THE REVIEWED COPY FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER