| Plan Review Notes For Permit 15030663 |
| Permit Number |
15030663 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-31 06:58:25 | 1) INDICATE THE TYPE OF PIPE BEING INSTALLED. THE | | | DESIGN PARAMETERS ON SHT. P1 REFER TO TABLE 402.4 (3) | | | WHICH IS FOR SCH. 40 STEEL PIPE BUT THE PLAN SHOWS PE | | | PIPE. CLARIFY. | | | 2) 2010 FUEL GAS CODE SEC.616.1 - GENERATOR SHALL MEET | | | THE REQUIREMENTS OF UL 2200 AND INTSALLED IN ACCORDANCE | | | W/ MANUF. INSTRUCTIONS AND NFPA 37. SUBMIT | | | DOCUMENTATION SHOWING COMPLIANCE WITH THESE STANDARDS. | | | THE PLANS ARE VAGUE AS TO COMPLIANCE W/UL2200. | | | 3)INDICATE ON THE PLANS IF THE EXISTING GAS METER IS | | | GOING TO REMAIN OR BE REMOVED. | | | 4) SHT. P1 SHOWS PE PIPE TO THE GENERATOR. PE PIPE CAN | | | ONLY BE USED OUTSIDE, UNDERGROUND PER THE 2010 FGC | | | SEC.404.15. | | | 5) SHT. P1 NOTE #20 REFERS TO 2004 GAS CODE. CLARIFY. | | | 6) INDICATE THE BTU LOAD OF THE GENERATOR. | | | 7) SUBMIT MANUF. SPECS FOR THE REGULATOR. REGULATORS | | | INSTALLED OUTDOORS SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|