Plan Review Notes
Plan Review Notes For Permit 15030663
Permit Number 15030663
Review Stop G
Sequence Number 1
Notes
Date Text
2015-03-31 06:58:251) INDICATE THE TYPE OF PIPE BEING INSTALLED. THE
 DESIGN PARAMETERS ON SHT. P1 REFER TO TABLE 402.4 (3)
 WHICH IS FOR SCH. 40 STEEL PIPE BUT THE PLAN SHOWS PE
 PIPE. CLARIFY.
 2) 2010 FUEL GAS CODE SEC.616.1 - GENERATOR SHALL MEET
 THE REQUIREMENTS OF UL 2200 AND INTSALLED IN ACCORDANCE
 W/ MANUF. INSTRUCTIONS AND NFPA 37. SUBMIT
 DOCUMENTATION SHOWING COMPLIANCE WITH THESE STANDARDS.
 THE PLANS ARE VAGUE AS TO COMPLIANCE W/UL2200.
 3)INDICATE ON THE PLANS IF THE EXISTING GAS METER IS
 GOING TO REMAIN OR BE REMOVED.
 4) SHT. P1 SHOWS PE PIPE TO THE GENERATOR. PE PIPE CAN
 ONLY BE USED OUTSIDE, UNDERGROUND PER THE 2010 FGC
 SEC.404.15.
 5) SHT. P1 NOTE #20 REFERS TO 2004 GAS CODE. CLARIFY.
 6) INDICATE THE BTU LOAD OF THE GENERATOR.
 7) SUBMIT MANUF. SPECS FOR THE REGULATOR. REGULATORS
 INSTALLED OUTDOORS SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION.
  