| Plan Review Notes For Permit 15030623 |
| Permit Number |
15030623 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-09 19:06:16 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 / 2008 NEC | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF ELECTRICAL PLANS. SHOWING | | | COMPLIANCE WITH THE 2008 NEC FOR REQUIRED RECEPTALCES, | | | LIGHTING OUTLETS AND PANEL LOCATION. PROVIDE A PANEL | | | SCHEDULE AND INDICATE THE CIRCUIT NUMBERS ON THE PLANS. | | | FBC 107.3.5.3 | | | | | | 2) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING | | | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | | RECORDS MANAGEMENT. | | | | | | 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 4) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | |
|