| Plan Review Notes For Permit 15030536 |
| Permit Number |
15030536 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-19 10:27:28 | 1) SUBMIT TWO COPIES OF MANUFACTURER'S | | | SPECIFICATIONS/INSTALLATION SHEETS FOR THE | | | GENERATOR.THE GENERATOR SHALL BE UL2200 COMPLIANT PER | | | THE FUEL GAS CODE SEC.616.1. | | | 2) THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH | | | THE MANUF. INSTALLATION INSTRUCTIONS AND NFPA 37. 2010 | | | FGC SEC.616.1. | | | 3) SHOW THE TERMINUS OF THE GAS VENT. THE LOCATION | | | SHALL COMPLY WITH THE 2010 FGC SEC. 503.6.4, 503.8. | | | 4) THE GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FEET | | | FROM OPENINGS IN THE EXTERIOR BUILDING WALLS AND AT | | | LEAST 5 FEET FROM STRUCTURES HAVING COMBUSTIBLE WALLS. | | | IF THE EXTERIOR WALL IS NOT 1 HOUR FIRE RATED THEN THE | | | GENERATOR SHALL BE A MIN. OF 5 FEET FROM THE EXTERIOR | | | PER NFPA 37 SEC. 4.1.4. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|