| Plan Review Notes For Permit 15030523 |
| Permit Number |
15030523 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-13 19:10:50 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL | | | PLAN TO SHOW EQUIPMENT , LOCATION OF EQUIPMENT AND DUCT | | | SYSTEMS PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. | | | | | | 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | | | | 3) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND | | | SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN | | | AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT | | | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. | | | | | | 4) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT | | | BEDROOMS. | | | | | | 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | |
|