| 2015-04-14 10:03:38 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRIC |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC 107.3.5.3 - SUBMIT TWO SETS OF AN ELECTRIC |
| | SERVICE RISER DIAGRAM WITH WIRE SIZES, CONDUIT DETAIL |
| | AND GROUNDING DETAIL. |
| | |
| | 2) FBC 107.3.5.3 - PROVIDE PANEL SCHEDULES AND SHOW |
| | CIRCUITS ON FLOOR PLAN. |
| | |
| | 3) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE |
| | PRESENT. |
| | |
| | 4) SPECIFY THE LOCATION OF THE ELECTRICAL SERVICE ON |
| | THE PLANS. FBC 107.2.1 |
| | |
| | 5) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE |
| | ELECTRICAL EQUIPMENT ON THE PLANS. |
| | |
| | 6) FBC-R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE |
| | FOLLOWING LOCATIONS: |
| | 1. IN EACH SLEEPING ROOM. |
| | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| | INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| | DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| | THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| | ALARMS IN THE INDIVIDUAL UNIT. |
| | |
| | 7) FBC-R 315.1 - PROVIDE CARBON MONOXIDE ALARMS WITHIN |
| | 10 FEET OF EACH SLEEPING ROOM. |
| | |
| | 8) NEC 210.8 (A) (1)-(8) - GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION REQUIRED. OUTDOOR OUTLET |
| | RECEPTACLES ARE REQUIRED TO BE GFCI PROTECTED. |
| | |
| | 9) NEC 406.8 - OUTDOOR RECEPTACLES ARE REQUIRED TO BE |
| | WEATHER PROOF. |
| | |
| | 10) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI |
| | PROTECTED. |
| | |
| | 11) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| | REQUIRED. |
| | |
| | 12) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE |
| | OUTLET FOR WITHIN 25' OF MECHANICAL EQUIPMENT. |
| | |
| | 13) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE |
| | REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE |
| | PLANS. |
| | |
| | 14) NEC 410.16 (A) - (C) - LUMINAIRES IN CLOTHES |
| | CLOSETS SHALL BE OF THE TYPE PERMITTED AND LOCATED AS |
| | REQUIRED. |
| | |
| | 15) FS 471 AND FAC 61G15 REQUIRES THE ENGINEER TO SIGN |
| | BY HAND THE LICENSEE'S HANDWRITTEN WRITTEN SIGNATURE ON |
| | THE PLANS. SIGNATURE STAMPS, COPIES OR OTHER FACSIMILES |
| | ARE NOT ACCEPTABLE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |