| Plan Review Notes For Permit 15030520 |
| Permit Number |
15030520 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-03-17 14:29:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. BASED ON AERIALS AND PAPA INFORMATION, THERE IS NO | | | PARAPET ON THIS STRUCTURE. | | | | | | ENGINEER'S CALCULATIONS INCLUDE A STATEMENT THAT THE | | | PARAPET HEIGHT >= 3' AND P3 CAN BE TAKEN AS P2. THIS | | | APPEARS TO BE AN ERROR. | | | | | | IF ENGINEER OR CONTRACTOR FEELS THAT THIS IS CORRECT, | | | PROVIDE A PHOTOGRAPH OR ROOF PLAN SHOWING THE 3' | | | PARAPET. IF THIS WAS LEFT ON THE PLAN INADVERTENTLY, | | | EITHER REVISE CALCS OR THE CALCS WILL BE REDLINED FOR | | | YOU UPON REQUEST. | | | | | | FBC 2010 RESIDENTIAL 301 |
|