| 2015-11-18 17:33:36 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1. FBC-E SECTION 502.3.8: RECESSED LUMINARIES INSTALLED |
| | IN THE BUILDING ENVELOPE SHALL BE IC RATED AND SEALED |
| | TO LIMIT THE LEAKAGE OF AIR FROM THE CONDITIONED SPACE |
| | TO THE NON-CONDITIONED SPACE. |
| | 2. FBC-E SECTION 505.2 LIGHTING CONTROLS (MANDATORY): |
| | YOU SHALL PROVIDE THE REQUIRED LIGHTING CONTROLS FOR |
| | ROOMS 107 - 114 AND 121 - 123. THERE MAY BE ADDITIONAL |
| | LOCATIONS WHICH I MAY HAVE MISSED SO REVIEW YOUR |
| | LIGHTING DESIGN TO COMPLY WITH SUCH REQUIREMENT. |
| | 3. FBC-E SECTION 505 ELECTRICAL POWER & LIGHTING |
| | SYSTEMS (MANDATORY): HAS NUMEROUS LIGHTING REQUIREMENTS |
| | WHICH MAY APPLY. |
| | 4. FBC-E YOU SHALL SUBMIT INTERIOR AND EXTERIOR |
| | LIGHTING POWER ALLOWANCES CHARTS INDICATING COMPLIANCE |
| | WITH LIGHTING POWER ALLOWANCES. |
| | 5. FBC-E 505.7.3: ALL FEEDER AND BRANCH CIRCUIT |
| | CALCULATIONS SHALL TAKE INTO ACCOUNT THE CODE REQUIRED |
| | VOLTAGE DROP MAXIMUMS. |
| | 6. FBC-E 505.7.4 COMPLETION REQUIREMENTS: A NOTE ON THE |
| | APPROVED PLANS SHALL INDICATE THAT WITHIN 30 DAYS OF |
| | SYSTEM ACCEPTANCE AN AS-BUILT SET OF ELECTRICAL |
| | DRAWINGS SHALL BE PROVIDED TO THE BUILDING OWNER. |
| | 7. NEC 110.16: ALL ELECTRICAL PANELS AND EQUIPMENT |
| | SHALL BE MARKED WITH AN ARCH-FLASH HAZARD WARNING |
| | DECAL. |
| | 8. NEC 210.62: THERE SHALL BE A 125 V. SINGLE PHASE 15 |
| | OR 20 AMP RECEPTACLE OUTLET FOR EVERY 12 FT. OR MAJOR |
| | PORTION OF SHOW WINDOW AREA MEASURED HORIZONTALLY. |
| | 9. NEC 215.5: YOU SHALL SUBMIT A SITE SPECIFIC FEEDER |
| | DIAGRAM SHOWING FEEDER DETAILS, LOAD CALCULATIONS, |
| | CONDUCTOR SIZING AND INSULATION. THIS SHALL INCLUDE THE |
| | LOAD FOR THE ADDITIONAL OUTLETS REQUIRED ABOVE. |
| | 10. NEC 230: YOU SHALL INDICATE ON THE FLOOR PLAN OR |
| | SITE PLAN THE LOCATION OF THE SERVICE EQUIPMENT AND ANY |
| | UTILITY TRANSFORMERS. IF AUXILIARY GENERATOR IS |
| | PROPOSED. MANUFACTURERS? DOCUMENTATION FOR THE |
| | GENERATOR SHALL BE SUBMITTED. |
| | 11. NEC 314.27(C): ALL FLOOR RECEPTACLES SHALL ME IN |
| | BOXES LISTED FOR THIS PURPOSE. |
| | 12. NEC 408.4: CIRCUIT DIRECTORY FOR PANEL "AC" SHALL |
| | BE PROVIDED. ALL ADDITIONAL SHOW WINDOW LOADS SHALL BE |
| | INCLUDED ON THE PANEL SCHEDULES. |
| | 13. NEC 408.58: ALL PANELS SHALL BE MARKED WITH THEIR |
| | OPERATING VOLTAGE AND PHASE DESIGNATION |
| | 14. NEC 600.5: EACH COMMERCIAL ESTABLISHMENT ACCESSIBLE |
| | TO PEDESTRIANS SHALL HAVE A DEDICATED SIGN OUTLET IN AN |
| | ACCESSIBLE LOCATION AT EVERY ENTRANCE ACCESSIBLE TO |
| | PEDESTRIANS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |