| 2015-04-08 07:45:46 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | THE FOLLOWING ITEMS ARE RECOMMENDED CHANGES / |
| | CLARIFICATIONS TO THE DESIGN OF THE PROPOSED RAMP. |
| | CLARIFICATIONS ARE REQUIRED, CHANGES ARE NOT MANDATORY |
| | FOR THIS RESIDENTIAL RAMP. PLEASE CALL ME TO DISCUSS. |
| | ALTHOUGH THE PROPOSED RAMP IS RESIDENTIAL, VOLUNTARY |
| | AND NOT SUBJECT TO FBC 2010 ACCESSIBILITY, PLEASE NOTE |
| | THAT THE REQUIREMENTS IN FBC 2010 ACCESSIBILITY ARE |
| | BASED ON FEDERAL ADA AND HAVE BEEN DEVELOPED BASED ON |
| | THE DESIGNS MOST USABLE BY THE DISABLED WHILE NOT |
| | CAUSING A HAZARD TO OTHERS. IF YOU WOULD LIKE DETAILS |
| | PROVIDED FOR YOU (FROM FBC 2010 ACCESSIBILITY), PLEASE |
| | ADVISE. |
| | |
| | 1. SHOW A SECTION OR ELEVATION OF PROPOSED |
| | CONSTRUCTION. IT APPEARS THAT THE HIGHEST POINT ON THE |
| | RAMP WILL BE 6" ABOVE GRADE; DETAIL IS TO PROVIDE THIS |
| | INFORMATION, FBC 107. |
| | |
| | 2. THE DETAIL PROVIDED SHOWS A PORTION OF THE LANDING |
| | IN THE RAMP. IT IS NOT CLEAR HOW THE RAMP TIES INTO THE |
| | LANDING. |
| | |
| | 3. THE HANDRAIL SHOWS A SMALL EXTENSION AT THE BOTTOM; |
| | SPECIFY. THE HANDRAIL SHOWS A TURN AT THE LANDING. A |
| | COMPLIANT DETAIL WAS PROVIDED BUT THE PLAN VIEW DOES |
| | NOT SHOW THE EXTENSION AT THE TOP. ASSISTANCE |
| | (MODIFICATION OF THE DETAIL) WILL BE PROVIDED FOR YOU |
| | UPON REQUEST. FBC 2010 ACCESSIBILITY 505.10.1. |
| | |
| | 4. THE WRITTEN DESCRIPTION STATES THAT THERE WILL BE A |
| | LANDING AT THE FRONT DOOR AND THE CONCRETE RAMP WILL |
| | "MATCH THE LANDING," BUT THE LANDING IS SHOWN WIDER |
| | THAN THE RAMP, SO INTENT IS NOT CLEAR. |
| | |
| | 5. SEE FBC 2010 405.9, EDGE PROTECTION; THIS IS |
| | REQUIRED TO PREVENT FALLING / SLIPPING OFF THE EDGE OF |
| | THE RAMP. ONE EXEMPTION TO THIS IS FBC 2010 |
| | ACCESSIBILITY 405.9(3), "EDGE PROTECTION SHALL NOT BE |
| | REQUIRED ON THE SIDES OF RAMP LANDINGS HAVING A |
| | VERTICAL DROP OFF OF 1/2 INCH MAXIMUM WITHIN 10 INCHES |
| | HORIZONTALLY OF THE MINIMUM LANDING AREA SPECIFIED IN |
| | 405.7." ANOTHER OPTION IS AN EXTENDED RAMP WIDTH. THIS |
| | IS SHOWN GRAPHICALLY IN FBC 2010 ACCESSIBILITY 405.9. |
| | |
| | 6. SEE FBC 2010 ACCESSIBILITY 505.10.1 FOR HANDRAIL |
| | EXTENSIONS AT TOP AND BOTTOM. |
| | |
| | 7. THE COMPANY NAME ON THE APPLICATION SHOULD BE |
| | CONSISTENT WITH THE LICENSE, FS 489. |
| | |
| | |