| 2015-06-19 11:05:47 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS |
| | CODE: 2010 FBC |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. PERMIT CAN NOT |
| | BE ISSUED WITHOUT THE ENERGY CALCULATIONS. SEC. |
| | 103.2.3.2 OF 2010 FBC-RESIDENTIAL. |
| | NOTE: I AM NOT ASKING FOR THE A/C INFORMATION. ENERGY |
| | CALCULATIONS AND EQUIPMENT SIZING CALCULATIONS ARE TWO |
| | DIFFERENT THINGS. |
| | |
| | 2- SIZE OF WINDOWS SHOWN ON THE WINDOW SCHEDULE ARE NOT |
| | SHOWN ON THE PRODUCT APPROVAL AND DON'T SEEM TO COMPLY |
| | WITH THE EGRESS REQUIREMENTS. CLEARLY SPECIFY TYPE AND |
| | SIZE OF ALL WINDOWS, INCLUDING THE BEDROOM WINDOWS TO |
| | VERIFY COMPLIANCE WITH SEC. 604 OF 2010 FBC-EXISTING |
| | BUILDING AND SEC. R310 OF 2010 FBC-RESIDENTIAL. NOTE: |
| | SEE OPENING SIZES REQUIRED FOR BEDROOMS IN THE SECOND |
| | FLOOR. |
| | NOTE: PROVIDE MANUFACTURER'S CHART SHOWING THE |
| | SPECIFIED SIZE OF WINDOW THAT COMPLIES WITH THE EGRESS |
| | REQUIREMENTS. |
| | |
| | 3- DOOR STRUCTURAL BUCK DETAIL. NEED TO PROVIDE FULL |
| | SUPPORT TO THE DOOR FRAME AS REQUIRED BY SEC. |
| | R612.10.2.1 OF 2010 FBC-RESIDENTIAL. SEE DETAILS ON |
| | EXTERIOR DOOR AND SLIDING GLASS DOORS PRODUCT APPROVALS |
| | AND REVISE AS REQUIRED. |
| | |
| | 4- PROVIDE CURRENT ICC EVALUATION REPORT FOR THE FOAM |
| | INSULATION SHOWN ON NEW SOFFIT DETAIL 1 ON SHEET A-1. |
| | SEC. R316 OF 2010 FBC-RESIDENTIAL. ESR-3102 REPORT |
| | SUBMITTED EXPIRED ON AUGUST OF 2013. |
| | |
| | 5- SPECIFY SIZE OF WINDOW MULLION TO VERIFY DESIGN |
| | PRESSURES. WINDOW SCHEDULE ONLY SPECIFIES THE LENGTH. |
| | SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 6- FLAT ROOF NOA 14-0224.03 SUBMITTED: |
| | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| | BE INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON |
| | LAST PAGE OF NOA. NEED CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | NOTE: ONLY APPROVED ASSEMBLIES WITH GENERAL LIMITATION |
| | #7 ALLOWS NAIL ENHANCING WITH RAS 117 CALCULATIONS. |
| | ASSEMBLIES WITH GENERAL LIMITATION #9 CAN NOT BE USED. |
| | SEE GENERAL LIMITATION #9 ON LAST PAGE OF NOA. |
| | |
| | 7- SHEET S1: ENGINEER TO PROVIDE ALL HIS INFORMATION AS |
| | REQUIRED BY CHAPTER 471 F.S. DRAWING WAS SUBMITTED ONLY |
| | WITH THE SEAL AND SIGNATURE AT THE BOTTOM OF THE PAGE. |
| | |
| | **** PLEASE REMOVE ANDF REPLACE ANY REVISED DRAWING. |
| | ALSO SUBMIT OLD DRAWINGS FOR REFERENCE. |
| | ***** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS |
| | |