2015-06-19 11:05:47RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: 2010 FBC
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. PERMIT CAN NOT
 BE ISSUED WITHOUT THE ENERGY CALCULATIONS. SEC.
 103.2.3.2 OF 2010 FBC-RESIDENTIAL.
 NOTE: I AM NOT ASKING FOR THE A/C INFORMATION. ENERGY
 CALCULATIONS AND EQUIPMENT SIZING CALCULATIONS ARE TWO
 DIFFERENT THINGS.
  
 2- SIZE OF WINDOWS SHOWN ON THE WINDOW SCHEDULE ARE NOT
 SHOWN ON THE PRODUCT APPROVAL AND DON'T SEEM TO COMPLY
 WITH THE EGRESS REQUIREMENTS. CLEARLY SPECIFY TYPE AND
 SIZE OF ALL WINDOWS, INCLUDING THE BEDROOM WINDOWS TO
 VERIFY COMPLIANCE WITH SEC. 604 OF 2010 FBC-EXISTING
 BUILDING AND SEC. R310 OF 2010 FBC-RESIDENTIAL. NOTE:
 SEE OPENING SIZES REQUIRED FOR BEDROOMS IN THE SECOND
 FLOOR.
 NOTE: PROVIDE MANUFACTURER'S CHART SHOWING THE
 SPECIFIED SIZE OF WINDOW THAT COMPLIES WITH THE EGRESS
 REQUIREMENTS.
  
 3- DOOR STRUCTURAL BUCK DETAIL. NEED TO PROVIDE FULL
 SUPPORT TO THE DOOR FRAME AS REQUIRED BY SEC.
 R612.10.2.1 OF 2010 FBC-RESIDENTIAL. SEE DETAILS ON
 EXTERIOR DOOR AND SLIDING GLASS DOORS PRODUCT APPROVALS
 AND REVISE AS REQUIRED.
  
 4- PROVIDE CURRENT ICC EVALUATION REPORT FOR THE FOAM
 INSULATION SHOWN ON NEW SOFFIT DETAIL 1 ON SHEET A-1.
 SEC. R316 OF 2010 FBC-RESIDENTIAL. ESR-3102 REPORT
 SUBMITTED EXPIRED ON AUGUST OF 2013.
  
 5- SPECIFY SIZE OF WINDOW MULLION TO VERIFY DESIGN
 PRESSURES. WINDOW SCHEDULE ONLY SPECIFIES THE LENGTH.
 SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 6- FLAT ROOF NOA 14-0224.03 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA. NEED CALCULATIONS TO MEET THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL.
 NOTE: ONLY APPROVED ASSEMBLIES WITH GENERAL LIMITATION
 #7 ALLOWS NAIL ENHANCING WITH RAS 117 CALCULATIONS.
 ASSEMBLIES WITH GENERAL LIMITATION #9 CAN NOT BE USED.
 SEE GENERAL LIMITATION #9 ON LAST PAGE OF NOA.
  
 7- SHEET S1: ENGINEER TO PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 F.S. DRAWING WAS SUBMITTED ONLY
 WITH THE SEAL AND SIGNATURE AT THE BOTTOM OF THE PAGE.
  
 **** PLEASE REMOVE ANDF REPLACE ANY REVISED DRAWING.
 ALSO SUBMIT OLD DRAWINGS FOR REFERENCE.
 ***** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved