| Plan Review Notes For Permit 15030482 |
| Permit Number |
15030482 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-26 10:56:13 | 1ST REVIEW: FBC 2010 | | | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER, GROUNDING | | | DETAIL TO FOOTING STEEL DOESN'T SEEM POSSIBPLE FOR THIS | | | JOB AS NEW FOOTING ARE NOT PROPOSED & 1/0 WIRE LIKELY | | | WILL NOT BE USED. ALSO PROVIDE ANEL SCHEDULES AND SHOW | | | CIRCUITS ON FLOOR PLAN. PLEASE RE-SUBMIT. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|