| 2015-04-20 18:46:36 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 2- FIRST FLOOR PLAN ON SHEET A-1 SHOWS DEMOLITION OF A |
| | MASONRY BEARING WALL. SUPPORTING THE SECOND STORY. |
| | ENGINEER OF RECORD TO PROVIDE COMPLETE SHORING DETAILS |
| | AND SPECIFICATIONS. SEC. 107.2.1.3 CITY AMENDMENTS. |
| | |
| | 3- PLANS SUBMITTED ARE MISSING THE DEMOLITION-PLAN D-1. |
| | PROVIDE DEMOLITION FLOOR PLAN. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 4- SHEET A-1: INFORMATION SHOWN ON FIRST AND SECOND |
| | FLOOR PLAN DOESN'T MATCH INFORMATION SUBMITTED FOR |
| | INTERIOR DEMOLITION PERMIT #15030483. ALL WALLS ARE NOT |
| | EXISTING AS STATED ON THE WALL LEGEND. THE FLOOR LAYOUT |
| | WAS CHANGED. REVISE AS REQUIRED. CLEARLY IDENTIFY ALL |
| | NEW WALLS, ETC. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. REVISE VALUATION TO INCLUDE ALL SCOPE OF |
| | WORK SHOWN ON REVISED PLANS. COORDINATE SCOPE OF WORK |
| | WITH ITEM #5 ABOVE. |
| | |
| | 6- SPECIFY SIZE OF NEW ENTRY DOOR. SEC. R311.2 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 7- CLEARLY SPECIFY TYPE AND SIZE OF ALL WINDOWS, |
| | INCLUDING THE BEDROOM WINDOWS TO VERIFY COMPLIANCE WITH |
| | SEC. 604 OF 2010 FBC-EXISTING BUILDING AND SEC. R310 OF |
| | 2010 FBC-RESIDENTIAL. NOTE: SEE OPENING SIZES REQUIRED |
| | FOR BEDROOMS IN THE SECOND FLOOR. |
| | |
| | 8- SPECIFY CARBON MONOXIDE ALARMS AND LOCATION WITHIN |
| | BEDROOMS AS REQUIRED BY SEC. R315 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | DOORS AND WINDOWS STRUCTURAL BUCKS SHOWING COMPLIANCE |
| | WITH SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL. NOTE: |
| | NEED TO PROVIDE WINDOW/DOOR FULL FRAME SUPPORT. |
| | |
| | 10- SHEET S-1: |
| | A) NEW PORCH: WHERE IS FOOTING SECTION #4 TAKEN AT?. I |
| | THIS FOR THE NEW PORCH. HOW IS THE FOOTING CONNECTED TO |
| | THE PORCH COLUMN SPECIFIED ON FLOOR PLAN. ENGINEER TO |
| | CLARIFY WHY SPECIFYING ONLY ONE #5 VERTICAL |
| | REINFORCEMENT FOR THE NEW PORCH COLUMNS. SEC. R401.2 OF |
| | 2010 FBC-RESIDENTIAL. |
| | |
| | B) PROVIDE ROOF FRAMING PLAN FOR THE NEW PORCH. SPECIFY |
| | FRAMING MEMBERS AND ALL CONNECTORS. SEC. R801.2 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | C) SPECIFY BEAM SUPPORTING THE SECOND FLOOR WHERE |
| | MASONRY WALL IS GOING TO BE REMOVED BY THE LIVING AREA. |
| | SEC. R601.2 OF 2010 FBC-RESIDENTIAL. |
| | |
| | D) SPECIFY ALL NEW LINTELS ABOVE NEW DOOR/WINDOW |
| | OPENINGS. SEC. R601.2 OF 2010 FBC-RESIDENTIAL. |
| | |
| | D) DESIGN LOAD ON ROOF FRAMING NOTES: SPECIFY THE ATTIC |
| | LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2010 |
| | FBC-RESIDENTIAL. SEE FOOTNOTES B AND G OF TABLE R301.5. |
| | |
| | E) ROOF SHEATHING NAILING PLAN: ROOF PORCH IS MISSING |
| | ROOF ZONE #3 AND DIMENSION "A" TO BE 4'-0" MIN. . SEE |
| | FOOTNOTE ON FIGURE R301.2(7) OF 2010 FBC-RESIDENTIAL. |
| | |
| | F) NEW ROOF OVER FIRST FLOOR. PROVIDE COMPLETE DETAIL |
| | AND SPECIFICATIONS FOR THE ATTIC CROSS VENTILATION |
| | SHOWING COMPLIANCE WITH SEC. R806 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | G) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | FIRST FLOOR SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH |
| | SEC. R703.1.3 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 11- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) WINDOW MULLIONS AND CLEARLY SPECIFY MULLION SIZE TO |
| | VERIFY DESIGN PRESSURES. SEC. R301.1 2010 |
| | FBC-RESIDENTIAL |
| | |
| | B) CONCRETE TILE FOAM. SEE TILE NOA FOR LISTED |
| | PRODUCTS. |
| | |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE PRODUCT APPROVAL COVER |
| | PAGE AND PAGE SHOWING THE CONNECTOR OR ENGINEER TO LIST |
| | THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE |
| | SPECIFIED CONNECTOR. |
| | |
| | D) ENTRY DOOR. |
| | |
| | 12- ALL PRODUCT APPROVALS TO BE REVIEWED AND APPROVED |
| | IN WRITING BY THE ENGINEER OF RECORD. SEC. 107.3.4.1 |
| | CITY AMENDMENTS. NOTE: CLARIFY WHO APPROVED THE PRODUCT |
| | APPROVAL SUBMITTED. ONLY APPROVED AND THE INITIALS WERE |
| | PROVIDED, BUT THERE IS NO INDICATION OF WHO REVIEWED |
| | THEM. |
| | |