Plan Review Notes
Plan Review Notes For Permit 15030466
Permit Number 15030466
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-10 13:15:021ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 2010, NEC 2008
  
 CORRECTIONS REQUIRED: (ITEMS MARKED IN GREEN ARE ONLY
 ENERGY CONSERVATION AND CONVENIENCE SUGGESTIONS) UNIT
 DL WAS REVIEWED FIRST, BUT COMMENTS MARKED TYPICAL
 APPLY TO ENTIRE PROJECT AND MAY BE REMEDIED WITH A
 NOTE.
 UNIT DL LOT 15
 1. THE ROUTING OF THE SERVICES MAY REQUIRE THAT AN
 EASEMENT BE RECORDED PER UNIT. IF SO, THESE WILL HAVE
 TO BE FILED AND RECORDED PRIOR TO FINAL INSPECTIONS.
 THIS WILL BE DETERMINED AND NOTED ON THE ELECTRICAL
 SITE PLAN. TYPICAL
 2. FBC-E SECTION 404.1 REQUIRES THAT A MINIMUM OF 50 OF
 THE LAMPS IN PERMANENTLY INSTALLED LUMINAIRES BE HIGH
 EFFICIENCY LAMPS. TYPICAL
 3. NEC 314.27(A) REQUIRES THAT BOXES IN CEILING FOR
 LUMINAIRES BE LISTED TO SUPPORT A MINIMUM OF 50LBS.
 TYPICAL
 4. NEC 314.27(D) STATES THAT OUTLET BOXES INTENDED FOR
 THE SOLE SUPPORT OF PADDLE FANS BE LISTED AND MARKED BY
 THE MANUFACTURER FOR THE PURPOSE. TYPICAL
 5. NEC 210.52(C)1 STATES THAT EVERY COUNTER SPACE
 GREATER THAN 12? SHALL BE AN OUTLET.
 6. THERE SHOULD BE LIGHTING CONTROL (4WAY SWITCH) FOR
 CORRIDOR LIGHT AT ENTRANCE TO REAR BEDROOM.
 7. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE MOUNTED IN
 A VISIBLE LOCATION AND BE PROVIDED WITH A PILOT LIGHT
 TO INDICATE WHEN LIGHT IS EITHER ON OR OFF.
 8. RELOCATE SMOKE DETECTORS SO THEY ARE NO LESS THAN
 36? FROM THE TIP OF A PADDLE FAN BLADE. TYPICAL
 9. FBC-E402.4.5 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES. TYPICAL
 10. ADJUST THE ELECTRICAL LEGEND SO THE DISCONNECT
 SYMBOL MATCHES THAT USED ON THE FLOOR PLAN. TYPICAL
 UNIT BR LOT 16
 11. NOTHING SPECIFIC NOTED FOR UNIT BR. SEE TYPICAL
 COMMENTS ABOVE. THIS SHEET IS LABELED BL BUT THE TITLE
 BLOCK IDENTIFIES IT AS BR.
 UNIT CL LOT 17
 12. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE MOUNTED IN
 A VISIBLE LOCATION AND BE PROVIDED WITH A PILOT LIGHT
 TO INDICATE WHEN LIGHT IS EITHER ON OR OFF.
 UNIT BR LOT 18
 13. NOTHING SPECIFIC NOTED FOR UNIT BR. SEE TYPICAL
 COMMENTS ABOVE.
 UNIT CR LOT 19
 14. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE MOUNTED IN
 A VISIBLE LOCATION AND BE PROVIDED WITH A PILOT LIGHT
 TO INDICATE WHEN LIGHT IS EITHER ON OR OFF.
 UNIT DR LOT 20
 15. IN OTHER UNITS THIS IS LABELED AS A PANTRY. IF IT
 IS TO BE A PANTRY IT IS CORRECT AS DRAWN, OTHERWISE PER
 NEC 210.52(C) AN OUTLET IS REQUIRED.
 16. THERE SHOULD BE LIGHTING CONTROL (4WAY SWITCH) FOR
 CORRIDOR LIGHT AT ENTRANCE TO REAR BEDROOM.
 17. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE MOUNTED IN
 A VISIBLE LOCATION AND BE PROVIDED WITH A PILOT LIGHT
 TO INDICATE WHEN LIGHT IS EITHER ON OR OFF.
 18. FBC-E402.4.5 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES. TYPICAL
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER