| 2016-02-10 13:15:02 | 1ST ELECTRICAL REVIEW NOTES: |
| | REVIEWED FOR COMPLIANCE WITH: |
| | FBC 2010, NEC 2008 |
| | |
| | CORRECTIONS REQUIRED: (ITEMS MARKED IN GREEN ARE ONLY |
| | ENERGY CONSERVATION AND CONVENIENCE SUGGESTIONS) UNIT |
| | DL WAS REVIEWED FIRST, BUT COMMENTS MARKED TYPICAL |
| | APPLY TO ENTIRE PROJECT AND MAY BE REMEDIED WITH A |
| | NOTE. |
| | UNIT DL LOT 15 |
| | 1. THE ROUTING OF THE SERVICES MAY REQUIRE THAT AN |
| | EASEMENT BE RECORDED PER UNIT. IF SO, THESE WILL HAVE |
| | TO BE FILED AND RECORDED PRIOR TO FINAL INSPECTIONS. |
| | THIS WILL BE DETERMINED AND NOTED ON THE ELECTRICAL |
| | SITE PLAN. TYPICAL |
| | 2. FBC-E SECTION 404.1 REQUIRES THAT A MINIMUM OF 50 OF |
| | THE LAMPS IN PERMANENTLY INSTALLED LUMINAIRES BE HIGH |
| | EFFICIENCY LAMPS. TYPICAL |
| | 3. NEC 314.27(A) REQUIRES THAT BOXES IN CEILING FOR |
| | LUMINAIRES BE LISTED TO SUPPORT A MINIMUM OF 50LBS. |
| | TYPICAL |
| | 4. NEC 314.27(D) STATES THAT OUTLET BOXES INTENDED FOR |
| | THE SOLE SUPPORT OF PADDLE FANS BE LISTED AND MARKED BY |
| | THE MANUFACTURER FOR THE PURPOSE. TYPICAL |
| | 5. NEC 210.52(C)1 STATES THAT EVERY COUNTER SPACE |
| | GREATER THAN 12? SHALL BE AN OUTLET. |
| | 6. THERE SHOULD BE LIGHTING CONTROL (4WAY SWITCH) FOR |
| | CORRIDOR LIGHT AT ENTRANCE TO REAR BEDROOM. |
| | 7. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE MOUNTED IN |
| | A VISIBLE LOCATION AND BE PROVIDED WITH A PILOT LIGHT |
| | TO INDICATE WHEN LIGHT IS EITHER ON OR OFF. |
| | 8. RELOCATE SMOKE DETECTORS SO THEY ARE NO LESS THAN |
| | 36? FROM THE TIP OF A PADDLE FAN BLADE. TYPICAL |
| | 9. FBC-E402.4.5 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. TYPICAL |
| | 10. ADJUST THE ELECTRICAL LEGEND SO THE DISCONNECT |
| | SYMBOL MATCHES THAT USED ON THE FLOOR PLAN. TYPICAL |
| | UNIT BR LOT 16 |
| | 11. NOTHING SPECIFIC NOTED FOR UNIT BR. SEE TYPICAL |
| | COMMENTS ABOVE. THIS SHEET IS LABELED BL BUT THE TITLE |
| | BLOCK IDENTIFIES IT AS BR. |
| | UNIT CL LOT 17 |
| | 12. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE MOUNTED IN |
| | A VISIBLE LOCATION AND BE PROVIDED WITH A PILOT LIGHT |
| | TO INDICATE WHEN LIGHT IS EITHER ON OR OFF. |
| | UNIT BR LOT 18 |
| | 13. NOTHING SPECIFIC NOTED FOR UNIT BR. SEE TYPICAL |
| | COMMENTS ABOVE. |
| | UNIT CR LOT 19 |
| | 14. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE MOUNTED IN |
| | A VISIBLE LOCATION AND BE PROVIDED WITH A PILOT LIGHT |
| | TO INDICATE WHEN LIGHT IS EITHER ON OR OFF. |
| | UNIT DR LOT 20 |
| | 15. IN OTHER UNITS THIS IS LABELED AS A PANTRY. IF IT |
| | IS TO BE A PANTRY IT IS CORRECT AS DRAWN, OTHERWISE PER |
| | NEC 210.52(C) AN OUTLET IS REQUIRED. |
| | 16. THERE SHOULD BE LIGHTING CONTROL (4WAY SWITCH) FOR |
| | CORRIDOR LIGHT AT ENTRANCE TO REAR BEDROOM. |
| | 17. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE MOUNTED IN |
| | A VISIBLE LOCATION AND BE PROVIDED WITH A PILOT LIGHT |
| | TO INDICATE WHEN LIGHT IS EITHER ON OR OFF. |
| | 18. FBC-E402.4.5 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. TYPICAL |
| | |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |