| Plan Review Notes For Permit 15030465 |
| Permit Number |
15030465 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-30 15:34:43 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENERGY FORM IS MISSING THE FOLLOWING | | | INFORMATION: OWNER, BUILDER NAME, PERMIT OFFICE ( CITY | | | OF WEST PALM BEACH ), JURISDICTION ( 604700 ). FBC | | | 107.2.1.4 | | | | | | 2) THE ENERGY CALCULATIONS APPEAR TO HAVE USED AN | | | INCORRECT ORIENTATION. THE 3080 FRONT DOOR DOOR FACES | | | EAST NOT SOUTH AND THE 8' X 8' SGD ( 64 SQFT ) FACES | | | WEST NOT NORTH. | | | | | | 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | FRONT DOOR IS FOR A GLAZED SINGLE FRENCH DOOR WHERE THE | | | GLASS AREA IS EQUAL OR GREATER THAN ONE THIRD OF THE | | | DOOR AREA. THIS DOOR IS REQUIRED TO BE INCLUDED IN THE | | | GLAZING CALCULATION AS A TOTAL FENESTRATION. FBC ENERGY | | | SECTION 405.5.3 | | | | | | 4) ON THE MECHANICAL PLANS FOR THE MADERA MODELS THE | | | 14" RETURN TRANSFER DUCT IS TOO SMALL FOR THE MASTER | | | BEDROOM SUITE. THERE ARE (2) 5", (1) 4" AND (1) 8" | | | SUPPLY DUCTS ENTERING THE MASTER SUITE WITH A TOTAL | | | CROSS SECTIONAL AREA OF 103". FBC-R M1602.4 REQUIRES | | | THE TRANSFER DUCT TO BE 1.5 TIMES THE CROSS SECTIONAL | | | AREA OF THE SUPPLY DUCTS ENTERING THE SUITE AND A ONE | | | INCH UNDERCUT OF THE DOOR. | | | |
|