Plan Review Notes
Plan Review Notes For Permit 15030465
Permit Number 15030465
Review Stop M
Sequence Number 1
Notes
Date Text
2015-04-30 15:34:43PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM IS MISSING THE FOLLOWING
 INFORMATION: OWNER, BUILDER NAME, PERMIT OFFICE ( CITY
 OF WEST PALM BEACH ), JURISDICTION ( 604700 ). FBC
 107.2.1.4
  
 2) THE ENERGY CALCULATIONS APPEAR TO HAVE USED AN
 INCORRECT ORIENTATION. THE 3080 FRONT DOOR DOOR FACES
 EAST NOT SOUTH AND THE 8' X 8' SGD ( 64 SQFT ) FACES
 WEST NOT NORTH.
  
 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FRONT DOOR IS FOR A GLAZED SINGLE FRENCH DOOR WHERE THE
 GLASS AREA IS EQUAL OR GREATER THAN ONE THIRD OF THE
 DOOR AREA. THIS DOOR IS REQUIRED TO BE INCLUDED IN THE
 GLAZING CALCULATION AS A TOTAL FENESTRATION. FBC ENERGY
 SECTION 405.5.3
  
 4) ON THE MECHANICAL PLANS FOR THE MADERA MODELS THE
 14" RETURN TRANSFER DUCT IS TOO SMALL FOR THE MASTER
 BEDROOM SUITE. THERE ARE (2) 5", (1) 4" AND (1) 8"
 SUPPLY DUCTS ENTERING THE MASTER SUITE WITH A TOTAL
 CROSS SECTIONAL AREA OF 103". FBC-R M1602.4 REQUIRES
 THE TRANSFER DUCT TO BE 1.5 TIMES THE CROSS SECTIONAL
 AREA OF THE SUPPLY DUCTS ENTERING THE SUITE AND A ONE
 INCH UNDERCUT OF THE DOOR.
  