2015-04-30 14:57:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE APPLICATION SPECIFIES THAT THIS IS THE CASSANDRA
 MODEL AND THAT IT IS LOCATED ON LOT 14. THE BUILDING
 PLANS INDICATE THAT LOT 14 IS AN END UNIT AND IS AN
 AVANTI MODEL. THE ENERGY CALCULATIONS SUBMITTED ARE FOR
 THE AVANTI MODEL. PLEASE CORRECT. FBC 107.2.1
  
 2) THE ENERGY FORM IS MISSING THE FOLLOWING
 INFORMATION: OWNER, BUILDER NAME, PERMIT OFFICE ( CITY
 OF WEST PALM BEACH ), JURISDICTION ( 604700 ). FBC
 107.2.1.4
  
 3) THE ENERGY CALCULATIONS APPEAR TO HAVE USED AN
 INCORRECT ORIENTATION FOR THE AVANTI MODEL ON LOT 14.
 THE 3080 ENTRY DOOR ON THE SIDE FACES SOUTH NOT EAST.
 THE WINDOWS ARE LOCATED ON THE EAST, WEST AND SOUTH
 SIDES OF THIS END UNIT. THE 64 SQFT SLIDING GLASS DOOR
 FACES WEST NOT NORTH. FBC 107.2.1
  
 4) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FRONT DOOR IS FOR A GLAZED SINGLE FRENCH DOOR WHERE THE
 GLASS AREA IS EQUAL OR GREATER THAN ONE THIRD OF THE
 DOOR AREA. THIS DOOR IS REQUIRED TO BE INCLUDED IN THE
 GLAZING CALCULATION AS A TOTAL FENESTRATION. FBC ENERGY
 SECTION 405.5.3
  
 5) THE END UNITS TYPICALLY REQUIRE LARGER HEATING AND
 COOLING LOADS THAN THE UNITS IN BETWEEN. THEY HAVE AN
 EXTRA EXTERIOR WALL WITH WINDOWS. REVIEW THE
 CALCULATIONS TO DETERMINE WHY ALL OF THE UNITS HAVE THE
 SAME LOADS. FBC 107.2.1