| Date |
Text |
| 2015-04-30 14:57:00 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE APPLICATION SPECIFIES THAT THIS IS THE CASSANDRA |
| | MODEL AND THAT IT IS LOCATED ON LOT 14. THE BUILDING |
| | PLANS INDICATE THAT LOT 14 IS AN END UNIT AND IS AN |
| | AVANTI MODEL. THE ENERGY CALCULATIONS SUBMITTED ARE FOR |
| | THE AVANTI MODEL. PLEASE CORRECT. FBC 107.2.1 |
| | |
| | 2) THE ENERGY FORM IS MISSING THE FOLLOWING |
| | INFORMATION: OWNER, BUILDER NAME, PERMIT OFFICE ( CITY |
| | OF WEST PALM BEACH ), JURISDICTION ( 604700 ). FBC |
| | 107.2.1.4 |
| | |
| | 3) THE ENERGY CALCULATIONS APPEAR TO HAVE USED AN |
| | INCORRECT ORIENTATION FOR THE AVANTI MODEL ON LOT 14. |
| | THE 3080 ENTRY DOOR ON THE SIDE FACES SOUTH NOT EAST. |
| | THE WINDOWS ARE LOCATED ON THE EAST, WEST AND SOUTH |
| | SIDES OF THIS END UNIT. THE 64 SQFT SLIDING GLASS DOOR |
| | FACES WEST NOT NORTH. FBC 107.2.1 |
| | |
| | 4) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| | FRONT DOOR IS FOR A GLAZED SINGLE FRENCH DOOR WHERE THE |
| | GLASS AREA IS EQUAL OR GREATER THAN ONE THIRD OF THE |
| | DOOR AREA. THIS DOOR IS REQUIRED TO BE INCLUDED IN THE |
| | GLAZING CALCULATION AS A TOTAL FENESTRATION. FBC ENERGY |
| | SECTION 405.5.3 |
| | |
| | 5) THE END UNITS TYPICALLY REQUIRE LARGER HEATING AND |
| | COOLING LOADS THAN THE UNITS IN BETWEEN. THEY HAVE AN |
| | EXTRA EXTERIOR WALL WITH WINDOWS. REVIEW THE |
| | CALCULATIONS TO DETERMINE WHY ALL OF THE UNITS HAVE THE |
| | SAME LOADS. FBC 107.2.1 |