| Notes |
| Date |
Text |
| 2015-04-30 16:21:28 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENERGY FORM IS MISSING THE FOLLOWING | | | INFORMATION: OWNER, BUILDER NAME, PERMIT OFFICE ( CITY | | | OF WEST PALM BEACH ), JURISDICTION ( 604700 ). FBC | | | 107.2.1.4 | | | | | | 2) THE ENERGY CALCULATIONS APPEAR TO HAVE USED AN | | | INCORRECT ORIENTATION. THE 8' X 8' SGD ( 64 SQFT ) | | | FACES WEST NOT NORTH. ALL OF THE WINDOWS WILL BE EAST | | | OR WEST IN THE INTERIOR UNITS OF THIS BUILDING AND NOT | | | NORTH OR SOUTH. | | | | | | 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | FRONT DOOR IS FOR A GLAZED SINGLE FRENCH DOOR WHERE THE | | | GLASS AREA IS EQUAL OR GREATER THAN ONE THIRD OF THE | | | DOOR AREA. THIS DOOR IS REQUIRED TO BE INCLUDED IN THE | | | GLAZING CALCULATION AS A TOTAL FENESTRATION. FBC ENERGY | | | SECTION 405.5.3 | | | | | | |
|