Plan Review Notes
Plan Review Notes For Permit 15030459
Permit Number 15030459
Review Stop M
Sequence Number 1
Notes
Date Text
2015-04-30 16:19:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM IS MISSING THE FOLLOWING
 INFORMATION: OWNER, BUILDER NAME, PERMIT OFFICE ( CITY
 OF WEST PALM BEACH ), JURISDICTION ( 604700 ). FBC
 107.2.1.4
  
 2) THE ENERGY CALCULATIONS APPEAR TO HAVE USED AN
 INCORRECT ORIENTATION. THE 8' X 8' SGD ( 64 SQFT )
 FACES WEST NOT NORTH. ALL OF THE WINDOWS WILL BE EAST
 OR WEST IN THE INTERIOR UNITS OF THIS BUILDING AND NOT
 NORTH OR SOUTH.
  
 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FRONT DOOR IS FOR A GLAZED SINGLE FRENCH DOOR WHERE THE
 GLASS AREA IS EQUAL OR GREATER THAN ONE THIRD OF THE
 DOOR AREA. THIS DOOR IS REQUIRED TO BE INCLUDED IN THE
 GLAZING CALCULATION AS A TOTAL FENESTRATION. FBC ENERGY
 SECTION 405.5.3
  
  