| Notes |
| Date |
Text |
| 2015-07-09 17:28:31 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) IN ADDITION TO THE MADERA MODEL, ON THE MECHANICAL | | | PLANS FOR THE CASANDRA MODELS THE 14" RETURN TRANSFER | | | DUCT IS TOO SMALL FOR THE MASTER BEDROOM SUITE. THERE | | | ARE (2) 5", (1) 4" AND (1) 8" SUPPLY DUCTS ENTERING THE | | | MASTER SUITE WITH A TOTAL CROSS SECTIONAL AREA OF 103". | | | FBC-R M1602.4 REQUIRES THE TRANSFER DUCT TO BE 1.5 | | | TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY DUCTS | | | ENTERING THE SUITE AND A ONE INCH UNDERCUT OF THE DOOR. | | | | | | 2) THE NEW MECHANICAL PLANS FOR THE MADERA MODEL ARE | | | REQUIRED TO HAVE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN ON THEM. FBC 107.2.1 | | | | | | 3) THE ENERGY CALCULATIONS FOR LOTS 9, 11 AND 13 | | | SPECIFY THE ROOFING AS COMPOSITE SHINGLES RATHER THAN | | | FLAT TILE. PLEASE REVISE. FBC 107.2.1 | | | | | | 4) WHEN UPLOADING NEW MECHANICAL PLANS BE SURE TO | | | UPLOAD THEM WITH THE DRAWINGS RATHER THAN THE | | | SUPPORTING DOCS. FBC 107.2.1.4 |
|