2015-07-09 17:28:31PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN ADDITION TO THE MADERA MODEL, ON THE MECHANICAL
 PLANS FOR THE CASANDRA MODELS THE 14" RETURN TRANSFER
 DUCT IS TOO SMALL FOR THE MASTER BEDROOM SUITE. THERE
 ARE (2) 5", (1) 4" AND (1) 8" SUPPLY DUCTS ENTERING THE
 MASTER SUITE WITH A TOTAL CROSS SECTIONAL AREA OF 103".
 FBC-R M1602.4 REQUIRES THE TRANSFER DUCT TO BE 1.5
 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY DUCTS
 ENTERING THE SUITE AND A ONE INCH UNDERCUT OF THE DOOR.
  
 2) THE NEW MECHANICAL PLANS FOR THE MADERA MODEL ARE
 REQUIRED TO HAVE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN ON THEM. FBC 107.2.1
  
 3) THE ENERGY CALCULATIONS FOR LOTS 9, 11 AND 13
 SPECIFY THE ROOFING AS COMPOSITE SHINGLES RATHER THAN
 FLAT TILE. PLEASE REVISE. FBC 107.2.1
  
 4) WHEN UPLOADING NEW MECHANICAL PLANS BE SURE TO
 UPLOAD THEM WITH THE DRAWINGS RATHER THAN THE
 SUPPORTING DOCS. FBC 107.2.1.4