| Plan Review Notes For Permit 15030458 |
| Permit Number |
15030458 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-27 14:04:09 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | 1) THE LANDSCAPE PLAN SHOWS THE WATER SUPPLY FOR THE | | | IRRIGATION SYSTEM AS CITY WATER. THE IRRIGATION SYSTEM | | | SHALL BE PROTECTED AGAINST BACKFLOW PER THE CITY'S | | | CROSS CONNECTION MANUAL. CONTACT STEVEN HUNTER AT | | | 561-805-2240 FOR THE PROPER TYPE OF BACKFLOW DEVICE TO | | | BE INSTALLED. FBC-R P2902 | | | 2) THE WATER HEATERS IN THE GARAGES SHALL BE PROTECTED | | | FROM VEHICLE IMPACT. FBC-R P2801.2 | | | 3) SHOW THE LOCATION OF THE CONTROLLER AND RAIN SENSOR | | | FOR THE IRRIGATION SYSTEM. A RAIN SENSOR IS REQUIRED ON | | | THE IRRIGATION SYSTEM PER FL. STATUTE 373.62. | | | |
|