Plan Review Notes
Plan Review Notes For Permit 15030458
Permit Number 15030458
Review Stop M
Sequence Number 1
Notes
Date Text
2015-04-27 18:12:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM IS MISSING THE FOLLOWING
 INFORMATION: OWNER, BUILDER NAME, PERMIT OFFICE ( CITY
 OF WEST PALM BEACH ), JURISDICTION ( 604700 ). FBC
 107.2.1.4
  
 2) THE ENERGY CALCULATIONS APPEAR TO HAVE USED AN
 INCORRECT ORIENTATION FOR THE AVANTI MODEL ON LOT 7.
 THE 3080 FRONT DOOR DOOR FACES NORTH NOT EAST AND THE
 8' X 8' SGD ( 64 SQFT ) FACES WEST NOT NORTH.
  
 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FRONT DOOR IS FOR A GLAZED SINGLE FRENCH DOOR WHERE THE
 GLASS AREA IS EQUAL OR GREATER THAN ONE THIRD OF THE
 DOOR AREA. THIS DOOR IS REQUIRED TO BE INCLUDED IN THE
 GLAZING CALCULATION AS A TOTAL FENESTRATION. FBC ENERGY
 SECTION 405.5.3
  
 4) ON THE MECHANICAL PLANS FOR THE MADERA AND CASSANDRA
 MODELS THE 14" RETURN TRANSFER DUCT IS TOO SMALL FOR
 THE MASTER BEDROOM SUITE. THERE ARE (2) 5", (1) 4" AND
 (1) 8" SUPPLY DUCTS ENTERING THE MASTER SUITE WITH A
 TOTAL CROSS SECTIONAL AREA OF 103". FBC-R M1602.4
 REQUIRES THE TRANSFER DUCT TO BE 1.5 TIMES THE CROSS
 SECTIONAL AREA OF THE SUPPLY DUCTS ENTERING THE SUITE
 AND A ONE INCH UNDERCUT OF THE DOOR.
  
 5) THE END UNITS TYPICALLY REQUIRE LARGER HEATING AND
 COOLING LOADS THAN THE UNITS IN BETWEEN. THEY HAVE AN
 EXTRA EXTERIOR WALL WITH WINDOWS. REVIEW THE
 CALCULATIONS TO DETERMINE WHY ALL OF THE UNITS HAVE THE
 SAME LOADS. FBC 107.2.1
  
  