| 2015-08-19 16:01:47 | PLAN REVIEW COMMENTS |
| | 5TH REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED. SEE COMMENTS |
| | BELOW. |
| | |
| | DENIED BY BUILDING - ( NOTE: THE PERMIT APPLICATION IS |
| | MISSING FROM THE CONSTRUCTION DOCUMENTS. A NEW |
| | REPLACEMENT APPLICATION IS REQUIRED. ) |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) REPEAT COMMENT. THE PLANS SPECIFY NEW IMPACT RATED |
| | DOORS AND WINDOWS. FBC 107.3.4 - PROVIDE TWO SETS OF |
| | PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| | TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| | INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| | PRESSURES FOR EACH OF THE WINDOW AND EXTERIOR DOOR |
| | TYPES. ONLY ONE SET OF PRODUCT APPROVALS WAS SUBMITTED |
| | FOR THE SINGLE HUNG WINDOWS (NOA NO. 14-0722.07). |
| | |
| | 2) REPEAT COMMENT. FBC - R 301.2.1.2 SUBMIT TWO COPIES |
| | OF AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM |
| | PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES, |
| | TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL |
| | LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO |
| | GLASS AND THE APPLICABLE SECTION NUMBER FROM THE |
| | INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE |
| | CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF |
| | THE RELATED FORMS INCLUDING |
| | THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE |
| | DEVICES. |
| | HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ |
| | |
| | 3) THE REVISED PLANS AND THE RESPONSE LETTER INDICATE |
| | THAT THE FRONT DOOR IS TO BE LARGE MISSILE IMPACT RATED |
| | TO ALLOW FOR EGRESS WHEN THE STORM PANELS ARE IN PLACE |
| | DURING THE THREAT OF A STORM PER FBC - R310.4. SUBMIT |
| | TWO SETS OF PRODUCT APPROVALS FOR THE 3' 0" X 6' 8" |
| | IMPACT RATED FRONT DOOR THAT HAVE BEEN REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| | TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| | INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| | PRESSURES. FBC 107.3.4 |
| | |
| | 4) ONE SET OF PRODUCT APPROVALS WERE PREVIOUSLY |
| | SUBMITTED FOR EACH OF THE FOLLOWING NON-IMPACT RATED |
| | DOORS FL#16106 AND A JELD-WEN CONTOURS PREMIUM STEEL |
| | WOOD EDGE HALF LITE OUTSWING DOOR WITH NO FL# INDICATED |
| | ON THE DOCUMENTS. TWO SETS OF PRODUCT APPROVALS WERE |
| | SUBMITTED FOR NON-IMPACT RATED DOORS (FL#15255.13) WITH |
| | THE LAST RESUBMITTAL. PLEASE CLARIFY WHICH OF THESE |
| | WILL BE INSTALLED. AN ADDITIONAL SET OF PRODUCT |
| | APPROVALS THAT HAVE BEEN REVIEWED BY THE DESIGNER OF |
| | RECORD WILL BE REQUIRED IF YOU WISH TO USE THE FIRST |
| | TWO MENTIONED AND A COVER SHEET WITH THE FL# IS |
| | REQUIRED FOR THE HALF LITE DOOR. FBC 107.2.1 |
| | |
| | 5) THE PERMIT APPLICATION IS MISSING FROM THE |
| | CONSTRUCTION DOCUMENTS. A NEW REPLACEMENT APPLICATION |
| | IS REQUIRED. |
| | |
| | 6) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| | ADDRESSED. |
| | |
| | |