| 2015-04-13 14:31:24 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING |
| | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS |
| | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER |
| | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. |
| | PROVIDE EQUIPMENT SIZING CALCULATIONS. THE MECHANICAL |
| | EQUIPMENT LISTED IN THE SCHEDULE ON SHEET 3 IS REQUIRED |
| | TO MATCH THE SIZING CALCULATIONS. |
| | |
| | 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT |
| | BEDROOMS. SPECIFY THE SIZES OF THE RETURN AIR TRANSFER |
| | GRILLS ON THE MECHANICAL PLAN. TRANSFER GRILLES SHALL |
| | USE 50 SQUARE INCHES (OF GRILLE AREA) TO 100 CFM (OF |
| | SUPPLY AIR) FOR SIZING THROUGH-THE-WALL TRANSFER |
| | GRILLES AND USING AN UNRESTRICTED 1 INCH UNDERCUTTING |
| | OF DOORS TO ACHIEVE PROPER RETURN AIR BALANCE. |
| | HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE |
| | REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS, |
| | EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL |
| | BE INCLUDED. |
| | |
| | 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 4) THE PLANS SHOW THE AIRHANDLER LOCATED IN A CLOSET. |
| | IF THE RETURN IS THROUGH A LOUVERED DOOR, SPECIFY THAT |
| | ON THE PLANS. FBC 107.2 |
| | |
| | |