| 2015-04-13 17:12:52 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER |
| | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2 |
| | FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN |
| | THAT SPACE. |
| | |
| | 2) NEC 210.8 (A)(6) RECEPTACLES SERVING COUNTERTOP |
| | SURFACES ARE REQUIRED TO BE GFCI PROTECTED. |
| | |
| | 3) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI |
| | PROTECTED. |
| | |
| | 4) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| | REQUIRED. |
| | |
| | 5) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE |
| | REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE |
| | PLANS. |
| | |
| | 6) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET |
| | FOR WITHIN 25' OF MECHANICAL EQUIPMENT. |
| | |
| | 7) THE CONDUIT AND WIRE SIZE FOR THE WEATHER HEAD SHOWN |
| | ON THE SERVICE RISER PLAN IS INCORRECT. NEC 310.15 (B) |
| | (6). |
| | |
| | 8) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | R314.3 LOCATION. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 1. IN EACH SLEEPING ROOM. |
| | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| | INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| | DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| | THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| | ALARMS IN THE INDIVIDUAL UNIT. |
| | |
| | 9) SPECIFY THE LOCATION OF THE ELECTRIC METER ON THE |
| | PLANS. FBC 107.2.1 |
| | |
| | 10) THE LUMINAIRES LOCATED IN THE BEDROOM CLOSETS SHALL |
| | MEET THE REQUIREMENTS OF NEC 410. |
| | |
| | 11) FBC 107.2.1 - INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 12) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| | ADDRESSED. |
| | |
| | |
| | |
| | |
| | |