| 2015-03-30 07:51:20 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTION |
| | DRAWINGS FOR THE LARGE MISSILE IMPACT RATED SINGLE HUNG |
| | WINDOWS ( FL17377 ) AS REQUIRED BY DCA RULE 9N-3. |
| | CIRCLE THE APPROPRIATE INSTALLATION TYPE ON THE PRODUCT |
| | APPROVAL. ( THROUGH FRAME OR FIN ) |
| | |
| | 2) THE INSTALLATION SCHEDULE THAT WAS SUBMITTED IS FOR |
| | OPENING PROTECTIVE DEVICES, SUCH AS, STORM PANELS. THE |
| | ANCHOR SPACING OF 8" O.C. IS NOT ACCEPTABLE FOR THE |
| | THROUGH FRAME INSTALLATION FOR WOOD. THE MAXIMUM |
| | SPACING IS 5" O.C. CENTER PER THE PRODUCT APPROVAL. FBC |
| | 301.1 |
| | |
| | 3) FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN |
| | LOADS/DESIGN PRESSURES PURSUANT TO FBC-CHAPTER 16 |
| | |
| | 4) SHOW THE INTERIOR WALLS AND DESIGNATE THE ROOMS ON |
| | THE WINDOW LOCATION FLOOR PLAN. THIS IS REQUIRED TO |
| | DETERMINE THAT THE BEDROOM EGRESS REQUIREMENTS ARE IN |
| | COMPLIANCE. |
| | SECTION 604 MEANS OF EGRESS |
| | 604.1 GENERAL. |
| | MEANS OF EGRESS FOR BUILDINGS UNDERGOING ALTERATION |
| | SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 601.1 AND |
| | THE SCOPING PROVISIONS OF CHAPTER 1 WHERE APPLICABLE. |
| | EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL |
| | DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5 PERCENT |
| | REDUCTION IN THE CLEAR OPENING DIMENSIONS OF |
| | REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED. |
| | |
| | 5) SUBMIT TWO SETS OF PLANS THAT SHOW THE EXISTING |
| | CABINET LAYOUT AND THE PROPOSED CABINET LAYOUT. IF |
| | ADDITIONAL COUNTER SPACE IS ADDED, THEN ADDITIONAL |
| | ELECTRICAL RECEPTACLES MAY BE REQUIRED. FBC 107.2.1 |
| | |
| | 6) SUBMIT TWO SETS OF PLANS THAT SPECIFY THE LOCATIONS |
| | AND EXTENT OF THE PROPOSED DRYWALL REPAIRS. FBC 107.2.1 |
| | |
| | 7) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING |
| | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |
| | 8) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 9) FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE |
| | VALUATION FOR THIS PROJECT ON THE PERMIT APPLICATION OF |
| | $3500.00 IS LOW. |
| | |
| | 10) FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN |
| | 10 FEET OF EACH SLEEPING ROOM. |
| | |
| | 11) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| | ADDRESSED. |
| | |
| | 12) RE-SUBMITTAL PROCEDURE |
| | YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO BE |
| | SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER |
| | DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED |
| | APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE |
| | REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN |
| | CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK |
| | WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER. |
| | ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED |
| | SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH |
| | THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED |
| | SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED |
| | FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS, |
| | RESUBMIT THOSE SHEETS. |
| | IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO |
| | (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS |
| | SHALL BE SUBMITTED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |