| 2015-03-16 11:58:49 | PERMIT # 15030405 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THIS PLAN HAS BEEN REVIEWED AND APPROVED WITH COMMENTS. | | | PROVISO: | | | 1) ALL REQUIRED FIRE ALARM DEVICES TO BE VERIFIED IN | | | THE FIELD. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR | | | THE INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | 2) EMERGENCY LIGHTING REQUIRED IN THE EARLY LEARNING | | | CENTER GALLERY - TO BE VERIFIED IN THE FIELD. | | | 3) A 2-HOUR SEPERATION IS REQUIRED FOR THE DEVISING | | | WALL BETWEEN THE OFFICES/WOOD SHOP AND THE PLANETARIUM. | | | (PLANS DO NOT SHOW THE CURRENT SEPARATION FOR THIS | | | WALL.) | | | | | | | | | ROY LINDOW | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4754 | | | |
|