Plan Review Notes
Plan Review Notes For Permit 15030368
Permit Number 15030368
Review Stop B
Sequence Number 1
Notes
Date Text
2015-04-07 17:09:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FOOTINGS TO BE MINIMUM 12" BELOW THE UNDISTURBED
 GROUND SURFACE, FBC 1809.4.
  
 2. THE INDEX SHEET FOR THE CALCULATIONS ARE TO BE IN
 THE FOLLOWING FORMAT PER FAC61G15-23.002(2)(B):
  
 WHEN AN ENGINEER MUST SEAL, SIGN AND DATE ENGINEERING
 SPECIFICATIONS OR CALCULATIONS UNDER THE PROVISIONS OF
 SECTION 471.025, F.S., AND SUBSECTION (1) OF THIS RULE,
 AN INDEX SHEET FOR ENGINEERING SPECIFICATIONS AND
 CALCULATIONS MAY BE USED. THE INDEX SHEET MUST BE
 SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL
 ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATIONS OR CALCULATIONS, WITH SUFFICIENT
 INFORMATION ON INDEX SHEET SO THAT THE USER WILL BE
 AWARE OF EACH PORTION OF THE SPECIFICATIONS OR
 CALCULATIONS FOR WHICH EACH PROFESSIONAL ENGINEER IS
 RESPONSIBLE. IN ADDITION, THE INDEX SHEET SHALL INCLUDE
 AT A MINIMUM:
 1. THE NAME, ADDRESS AND LICENSE NUMBER OF EACH
 ENGINEER IN RESPONSIBLE CHARGE OF THE PRODUCTION OF ANY
 PORTION OF THE CALCULATIONS OR SPECIFICATIONS.
 2. IDENTIFICATION OF THE PROJECT, BY ADDRESS OR BY LOT
 NUMBER, BLOCK NUMBER, SECTION OR SUBDIVISION AND CITY
 OR COUNTY.
 3. IDENTIFICATION OF THE APPLICABLE BUILDING CODE AND
 CHAPTER(S) THAT THE DESIGN IS INTENDED TO MEET.
 4. IDENTIFICATION OF ANY COMPUTER PROGRAM USED FOR
 ENGINEERING THE SPECIFICATIONS OR CALCULATIONS.
  
 3. THE PROPOSED IMPROVEMENT IS TO RESIST FLOOD LOADS AS
 THIS IS LOCATED IN A SPECIAL HAZARD FLOOD ZONE,
 FBC1612.2. REVISE DESIGN CRITERIA.
  
  
  
  