| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE |
| | REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH |
| | RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN |
| | CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE |
| | DIGITAL PLANS. |
| | |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE |
| | REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH |
| | RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN |
| | CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE |
| | DIGITAL PLANS. |
| | |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | PAGE A1-DL, LOT 28 |
| | 1. PER YOUR OWN AREA CALCS, THE SQUARE FOOTAGE FOR THE |
| | CONDITIONED SPACE IS 1867, THEREFORE 5.6 KW LOAD. |
| | 2. THIS CO DETECTOR SHALL BE RELOCATED TO BE GREATER |
| | THAN 3' FROM THE BATHROOM DOOR AND NO MORE THAN 10' |
| | FROM THE BEDROOM DOOR. |
| | 3. PER NEC 210.52(C), AN OUTLET IS MISSING IN THIS |
| | COUNTER AREA. |
| | 4. PER NEC 210.52(H), AN OUTLET IS MISSING IN THE HALL |
| | AREA |
| | 5. PER NEC 314.27, LUMINAIRE OUTLET INSTALLED IN |
| | CEILINGS SHALL BE RATED TO SUPPORT A MINIMUM OF 50# |
| | .PAGE A1-CL LOTS 29 & 31 |
| | 1. PER YOUR OWN AREA CALCS, THE SQUARE FOOTAGE FOR THE |
| | CONDITIONED SPACE IS 1777, THEREFORE 5.3 KW LOAD. |
| | 2. PER NEC 210.52(C), AN OUTLET IS MISSING IN THIS |
| | COUNTER AREA. |
| | 3. PER NEC 210.52(A), THIS WALL IS MISSING AN OUTLET. |
| | 4. A SINGLE CO DETECTOR PROPERLY SPACED 3' AWAY FROM |
| | ANY SOURCE OF FORCED AIR OR THE DOOR TO THE SHOWER IS |
| | SUFFICIENT. CO DETECTOR SHALL BE WITHIN 10? OF THE |
| | BEDROOM DOOR |
| | 5. PER NEC 314.27, LUMINAIRE OUTLET INSTALLED IN |
| | CEILINGS SHALL BE RATED TO SUPPORT A MINIMUM OF 50# |
| | PAGE A1-BL, LOT 30 |
| | 1. THIS IS AN INTERIOR UNIT. THIS OUTLET WILL NOT BE |
| | POSSIBLE |
| | 2. A SINGLE CO DETECTOR PROPERLY SPACED 3' AWAY FROM |
| | ANY SOURCE OF FORCED AIR OR THE DOOR TO THE SHOWER IS |
| | SUFFICIENT. CO DETECTOR SHALL BE WITHIN 10? OF THE |
| | BEDROOM DOOR |
| | 3. PER NEC 314.27, LUMINAIRE OUTLET INSTALLED IN |
| | CEILINGS SHALL BE RATED TO SUPPORT A MINIMUM OF 50# |
| | PAGE A1-BR, LOTS 32 & 34 |
| | 1. PER YOUR OWN AREA CALCS, THE SQUARE FOOTAGE FOR THE |
| | CONDITIONED SPACE IS 1764, THEREFORE 5.3 KW LOAD. |
| | 2. THIS IS AN INTERIOR UNIT. THIS OUTLET WILL NOT BE |
| | POSSIBLE |
| | 6. A SINGLE CO DETECTOR PROPERLY SPACED 3' AWAY FROM |
| | ANY SOURCE OF FORCED AIR OR THE DOOR TO THE SHOWER IS |
| | SUFFICIENT. CO DETECTOR SHALL BE WITHIN 10? OF THE |
| | BEDROOM DOOR |
| | 3. PER NEC 314.27, LUMINAIRE OUTLET INSTALLED IN |
| | CEILINGS SHALL BE RATED TO SUPPORT A MINIMUM OF 50# |
| | PAGE A1-CR, LOT 33 |
| | 1. PER YOUR OWN AREA CALCS, THE SQUARE FOOTAGE FOR THE |
| | CONDITIONED SPACE IS 1777, THEREFORE 5.3 KW LOAD. |
| | 2. PER NEC 210.52(C), AN OUTLET IS MISSING IN THIS |
| | COUNTER AREA. |
| | 3. PER NEC 210.52(A), THIS WALL IS MISSING AN OUTLET. |
| | 7. A SINGLE CO DETECTOR PROPERLY SPACED 3' AWAY FROM |
| | ANY SOURCE OF FORCED AIR OR THE DOOR TO THE SHOWER IS |
| | SUFFICIENT. CO DETECTOR SHALL BE WITHIN 10? OF THE |
| | BEDROOM DOOR |
| | 4. PER NEC 314.27, LUMINAIRE OUTLET INSTALLED IN |
| | CEILINGS SHALL BE RATED TO SUPPORT A MINIMUM OF 50# |
| | PAGE A1-DR LOT 35 |
| | 1. PER YOUR OWN AREA CALCS, THE SQUARE FOOTAGE FOR THE |
| | CONDITIONED SPACE IS 1867, THEREFORE 5.6 KW LOAD. |
| | 2. THIS CO DETECTOR SHALL BE RELOCATED TO BE GREATER |
| | THAN 3' FROM THE BATHROOM DOOR AND NO MORE THAN 10' |
| | FROM THE BEDROOM DOOR. |
| | 3. PER NEC 210.52(C), AN OUTLET IS MISSING IN THIS |
| | COUNTER AREA. |
| | 4. PER NEC 210.52(H), AN OUTLET IS MISSING IN THE HALL |
| | AREA |
| | 5. PER NEC 314.27, LUMINAIRE OUTLET INSTALLED IN |
| | CEILINGS SHALL BE RATED TO SUPPORT A MINIMUM OF 50# |
| | |
| | |
| | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER |