2015-07-24 13:59:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2. THE EXPOSURE CATEGORY
 FOR THIS PROJECT IS SPECIFIED AS 'B' AND IT IS EXPOSURE
 CATEGORY 'C'. FBC-R301.2.1.4
  
 2) THE 34-5 SH WINDOW ( MARK #8 ) ON A1-DL IS AN EGRESS
 WINDOW, ALTHOUGH IT IS NOT SPECIFIED AS SUCH IN THE
 WINDOW SCHEDULE.
  
 3) R803.2.3.1 SHEATHING FASTENINGS.
 WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO
 ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. RING-SHANK NAILS SHALL HAVE THE FOLLOWING
 MINIMUM DIMENSIONS:
  
 1. 0.113 INCH NOMINAL SHANK DIAMETER.
  
 2. RING DIAMETER OF 0.012 OVER SHANK DIAMETER.
  
 3. 16 TO 20 RINGS PER INCH.
  
 4. 0.280 INCH FULL ROUND HEAD DIAMETER.
  
 5. 2 INCH NAIL LENGTH.
  
 WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G <
 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL BE
 4 INCHES ON CENTER IN NAILING ZONE 3 IN ACCORDANCE WITH
 FIGURE R803.2.3.1 WHERE VASD AS DETERMINED IN
 ACCORDANCE WITH SECTION R301.2.1.3 IS 130 MPH OR
 GREATER.
  
 4) R401.4 SOIL TESTS. WHERE QUANTIFIABLE DATA CREATED
 BY ACCEPTED SOIL SCIENCE METHODOLOGIES INDICATE
 EXPANSIVE, COMPRESSIBLE, SHIFTING OR OTHER QUESTIONABLE
 SOIL CHARACTERISTICS ARE LIKELY TO BE PRESENT, THE
 BUILDING OFFICIAL SHALL DETERMINE WHETHER TO REQUIRE A
 SOIL TEST TO DETERMINE THE SOIL'S CHARACTERISTICS AT A
 PARTICULAR LOCATION. THIS TEST SHALL BE DONE BY AN
 APPROVED AGENCY USING AN APPROVED METHOD. SUBMIT TWO
 COPIES OF A SIGNED AN SEALED SUB-SURFACE SOIL
 INVESTIGATION REPORT.
  
 5) SHOW COMPLIANCE WITH FBC-R318.1 FOR TERMITE
 PROTECTION.
  
 6) THE NOTE ON SHEET A2-DL, " FILLED CELL W/1#5 VERT @
 72" O.C. MAXIMUM EXCEPT WHERE NOTED TYP." IS NOT CLEAR.
 THE ARROW IS POINTING TO THE 2 HOUR RATED FIRE WALL.
 THE SPACING OF THE FILLED CELLS IN THIS WALL ARE MORE
 THAN 9 FEET. CLARIFY.
  
 7) THERE DOES NOT APPEAR TO BE AN ATTACHMENT DETAIL FOR
 THE LEDGER THAT IS CARRYING THE FLOOR TRUSSES THAT ARE
 PERPENDICULAR TO THE 2 HOUR FIRE WALL THAT IS SHOWN ON
 THE 2ND FLOOR FRAMING PLAN ON A2-DL. FBC-R301.1
  
 8) SHOW COMPLIANCE WITH FBC-R312.3, ON THE STAIR
 SECTION ON D2, WHICH REQUIRES THE TRIANGULAR OPENINGS
 FORMED BY THE RISER, TREAD AND BOTTOM RAIL OF A GUARD
 TO REJECT THE PASSAGE OF A SPHERE 6 INCHES IN DIAMETER.
  
 9) ON THE OPTIONAL PATIO PLAN ON SHEET A12, PROVIDE
 ATTACHMENT DETAILS FOR THE TRUSS TO BEAM AND OUTLOOKERS
 TO RAKE BEAM CONNECTIONS. SPECIFY THE ROOF SLOPE.
 SPECIFY THE FOOTER FOR THE SINGLE REINFORCED FILLED
 CELL THAT IS AGAINST THE EXTERIOR TOWNHOUSE WALL AND
 THE ATTACHMENT OF THE TRUSS TOP CORD TO THIS WALL.
 SPECIFY THE ATTACHEMENTS OF THE BEAMS, WALLS AND
 FOOTINGS TO THE MAIN STRUCTURE. FBC 107.2.1
  
 10) PROVIDE A DETAIL OF THE OVERHANG DETAIL AT THE
 GABLE RAKE BEAMS SHOWING ALL CONNECTIONS. FBC-R301.1
 DETAIL 11/S6 IS SPECIFIED ON A2-BR, HOWEVER, IT IS
 BLANK.
  
 11) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED TO
 INSTALL THE CONCRETE ROOF TILE AND MEET THE REQUIRED
 OVERTURN MOMENT. DETAIL A/D1 STATES THAT IT WILL BE
 NAILED OR SCREWED. FBC-R 905.3 & 301.1
  
 12) INDICATE WHICH OF THE ATTACHMENT METHODS AND THE
 CORRESPONDING ATTACHMENT RESISTANCE LISTED IN THE ROOF
 TILE PRODUCT APPROVAL WILL BE USED. IF AN ADHESIVE IS
 USED, SUBMIT TWO SETS OF PRODUCT APPROVALS FOR IT. FBC
 107.2.1 AND DCA RULE 9N-3
  
 13) REVIEW THE MAXIMUM DESIGN PRESSURES IN THE PRODUCT
 APPROVALS TO INSURE THEY ARE ADEQUATE FOR THE HIGHER
 PRESSURES REQUIRED IN EXPOSURE CATEGORY C. CIRCLE THE
 DESIGN PRESSURES FOR THE COMPONENTS THAT WILL BE USED
 IN THE TABLES THAT ARE IN THE PRODUCT APPROVALS. FBC-R
 301.2.1 & FBC 107.2.1
  
 14) THE TRUSS LAYOUT PLAN THAT WAS SUBMITTED IS NOT
 TOTALLY LEGIBLE. SUBMIT LEGIBLE SIGNED AND SEALED FLOOR
 AND ROOF TRUSS LAYOUT PLANS AND FLOOR AND ROOF TRUSS
 DRAWINGS THAT HAVE BEEN REVIEW AND APPROVED BY THE
 DESIGNER OF RECORD. YOU MAY ELECT TO DEFER THE
 SUBMITTAL OF THE LAYOUT PLANS AND TRUSS DRAWINGS FOR
 REVIEW TO A LATER DATE THAT IS PRIOR TO TRUSS
 INSTALLATION.
  
 15) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  