Plan Review Notes
Plan Review Notes For Permit 15030360
Permit Number 15030360
Review Stop E
Sequence Number 3
Notes
Date Text
2015-06-15 10:19:066/15/2015
 PROJECT: FERGUSON SHOWROOM
 PERMIT#: 13110271
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW REVISION# 15030360
 ACTION: DENIED
  
 1) FBC, WPB AMENDMENTS 107.2.1
 THE REVISED PLANS ARE NOT ALL SIGNED OR SEALED. SHEET
 II-E-4-0 IS NOT SIGNED OR SEALED. PROVIDE A NEW SIGNED
 SEALED SHEET FOR REPLACEMENT. ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
 A) 471.025 668.001-668.006.
 ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR
 DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING
 FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL.
  
 2) 2011 EDITION OF THE NEC 220.43(B)EX: IF THE TRACK
 LIGHTING IS SUPPLIED THROUGH A DEVICE THAT LIMITS THE
 CURRENT TO THE TRACK, THE LOAD SHALL BE PERMITTED TO BE
 CALCULATED BASED ON THE RATING OF THE DEVICE USED TO
 LIMIT THE CURRENT. THE STATE OF FLORIDA AND THE CITY OF
 WEST PALM BEACH CURRENTLY RECOGNIZE ONLY THE 2008
 EDITION OF THE NEC. THERE IS NO SUCH EXCEPTION IN THE
 THE 2008 NEC. THE ENGINEER HAS FORMALLY REQUESTED VIA
 LETTER ATTACHED TO USE THE EXCEPTION IN THE 2011 NEC TO
 ALLOW THE USE OF A CURRENT LIMITING DEVICE FOR ALL
 TRACK LIGHTING ON THIS PROJECT. WE HAVE AGREED TO
 APPROVE THE USE OF THIS DEVICE UNDER THE 2011 NEC
 220.43(B) EXCEPTION IN THIS INSTANCE.
  
 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR ALL LOW VOLTAGE SPECIALTY PERMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  