| Plan Review Notes For Permit 15030360 |
| Permit Number |
15030360 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-13 10:07:38 | 1) THE GAS PLAN IS NOT SIGNED AND SEALED AS REQUIRED BY | | | F.S. 471 & F.A.C RULE 61G15-23.002. SEE SHT.P1-2. | | | 2) SHT.II-P1-2 - SIZE EACH SECTION OF PIPE ON THE | | | RISER.2010 FBC-FUEL GAS SEC.402.4.1 & 402.4.2. | | | 3) THE MANUFACURER'S SPECIFICATION SHEETS THAT WERE | | | SUBMITTED FOR THE GAS EQUIPMENT ARE INADEQUATE. THE | | | SPECIFICATIONS DO NOT SHOW THAT THE EQUIPMENT IS LISTED | | | AND LABELED PER THE 2010 FBC-FUEL GAS, SEC.301.3, | | | 301.5. REFER TO THE DEFINITION OF "LISTED" AND "LABELED | | | " IN FBC-FUEL GAS, SEC.202. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|