Plan Review Notes
Plan Review Notes For Permit 15030360
Permit Number 15030360
Review Stop E
Sequence Number 2
Notes
Date Text
2015-05-07 14:33:345/7/2015
 PROJECT: FERGUSON SHOWROOM
 PERMIT#: 13110271
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW REVISION# 15030360
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) FBC, WPB AMENDMENTS 107.2.1
 THE REVISED PLANS ARE NOT SIGNED OR SEALED. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 A) 471.025 668.001-668.006.
 ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR
 DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING
 FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL.
  
 2) NEC 220.43(B)
 REVISE THE BRANCH CIRCUIT LOAD FOR THE TRACK LIGHTING
 THROUGHOUT. A SINGLE 20AMP BRANCH CIRCUIT CAN CARRY A
 MAXIMUM OF 25 LINIAL FT. THERE ARE SECTIONS OF TRACK
 CONNECTED TO A SINGLE 120V 20AMP BRANCH CIRCUIT IN
 EXCESS OF 80 LINIAL FT. SEE NEC 220.43(B)
 THE EXCEPTION REFERRED TO IN THE ENGINEER'S RESPOSE TO
 THE PREVIOUS COMMENTS IS BASED ON THE 2011 EDITION OF
 THE NATIONAL ELECTRICAL CODE. THE STATE OF FLORIDA AND
 THE CITY OF WEST PALM BEACH CURRENTLY RECOGNIZE ONLY
 THE 2008 EDITION. THERE IS NO SUCH EXCEPTION IN THE THE
 2008 EDITION OF THE NEC. PLEASE REVISE THE PLAN
 ACCORDINGLY.
  
 3)NEC 700.12
 REVISE THE BRANCH CIRCUITRY FEEDING EMERGENCY AND EXIT
 LIGHTING THROUGHOUT. THE BRANCH CIRCUIT FEEDING
 EMERGENCY AND EXIT LIGHTING SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR LOW VOLTAGE SPECIALTY PERMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  