| 2015-05-07 14:33:34 | 5/7/2015 |
| | PROJECT: FERGUSON SHOWROOM |
| | PERMIT#: 13110271 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW REVISION# 15030360 |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) FBC, WPB AMENDMENTS 107.2.1 |
| | THE REVISED PLANS ARE NOT SIGNED OR SEALED. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | A) 471.025 668.001-668.006. |
| | ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR |
| | DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING |
| | FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS |
| | PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE |
| | SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH |
| | SAID SEAL. |
| | |
| | 2) NEC 220.43(B) |
| | REVISE THE BRANCH CIRCUIT LOAD FOR THE TRACK LIGHTING |
| | THROUGHOUT. A SINGLE 20AMP BRANCH CIRCUIT CAN CARRY A |
| | MAXIMUM OF 25 LINIAL FT. THERE ARE SECTIONS OF TRACK |
| | CONNECTED TO A SINGLE 120V 20AMP BRANCH CIRCUIT IN |
| | EXCESS OF 80 LINIAL FT. SEE NEC 220.43(B) |
| | THE EXCEPTION REFERRED TO IN THE ENGINEER'S RESPOSE TO |
| | THE PREVIOUS COMMENTS IS BASED ON THE 2011 EDITION OF |
| | THE NATIONAL ELECTRICAL CODE. THE STATE OF FLORIDA AND |
| | THE CITY OF WEST PALM BEACH CURRENTLY RECOGNIZE ONLY |
| | THE 2008 EDITION. THERE IS NO SUCH EXCEPTION IN THE THE |
| | 2008 EDITION OF THE NEC. PLEASE REVISE THE PLAN |
| | ACCORDINGLY. |
| | |
| | 3)NEC 700.12 |
| | REVISE THE BRANCH CIRCUITRY FEEDING EMERGENCY AND EXIT |
| | LIGHTING THROUGHOUT. THE BRANCH CIRCUIT FEEDING |
| | EMERGENCY AND EXIT LIGHTING SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA |
| | AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR LOW VOLTAGE SPECIALTY PERMITS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |